2.3.
OPERATOR INFORMATION AND FUNCTIONS
In general, the F090-A-PL will always act at Operator level.
Fig. 3: Example of display information during process.
For the Operator, the following functions are available (if activated):
▪
Display value and measuring unit
This is the main display information of the F090-A-PL. After selecting any other information, it
will always return to this main display automatically.
▪
Display actual mA value (if activated)
After pressing SELECT, the actual input current (mA) will be displayed.
▪
Display 0% / 100% (if activated)
After pressing SELECT a few times, the 0% value (=4mA) and 100% value (=20mA) will be
displayed.
▪
Under range / over range
If the input current is in-
between 3.5mA and 3.75mA “low range“ will be displayed.
If the input current is in-between 3.75mA and 4mA the value corresponding to 4mA will be
displayed.
If the input current is in-between 20 mA and 22mA the value will be extrapolated.
If the input current is above 22mA the value “high range” will be displayed.