FW-F090-A-PL-M_v0403_07_EN.docx
Page 11
3.2.2.
OVERVIEW FUNCTIONS SETUP LEVEL
SETUP FUNCTIONS AND VARIABLES
1
DISPLAY
11
UNIT
mL - L
–
nL - M3 - nM3 - mg - g - kg - ton - gal - sgal - igal - lb -
bbl - cf - scf - p - rev - °C - °F - °K - % - m - mm - cm - mtr - inch
- ft - psi - mbar - bar - barg - mmwk - mmwc - cmwk - cmwc -
mwk - mwc - inwc - ftwc - Ph - mV - no unit.
12
TIME UNIT
sec - min - hour - day - no unit (-----)
13
DECIMALS
0 - 1 - 2 - 3 - 4 - 5 (Ref: displayed value)
14
OFFSET
-99.999 to +199.999
15
SPAN
0.00001 to 199,999 unit/time-unit
16
DIRECTION
reverse - normal
17
CURRENT
on - off
18
PERCENTAGE
on - off
19
BARGRAPH
on - off
2
BACKLIGHT
21
BACKLIGHT (optional)
off - green - amber
22
BL. BRIGHTNESS
1 - 5
3
SENSOR
31
FORMULA
interpolation, square root
32
FILTER
00 - 99
33
CALIBRATE LOW - 4mA
default - set - calibrate
34
CALIBRATE HIGH - 20mA
default - set - calibrate
4
OTHERS
41
MODEL
F090-A
42
SOFTWARE VERSION
03-03-xx
43
SERIAL NO.
44
PASSWORD
0000 - 9999
45
TAGNUMBER
0000000 - 9999999
3.2.3.
EXPLANATION OF SETUP-FUNCTIONS
1 - DISPLAY
UNIT
11
SETUP - 21 determines the measurement unit to be displayed.
The following units can be selected:
mL - L
– nL - M3 - nM3 - mg - g - kg - ton - gal - sgal - igal - lb -
bbl
– cf = scf - p - rev - °C - °F - °K - % -
m - mm - cm - mtr - inch -
ft - psi - mbar = bar - barg - mmwk - mmwc - cmwk - cmwc - mwk -
mwc - inwc
–
ftwc - Ph - mV - no unit.
Alteration of the measurement unit will have consequences for other
SETUP-level values.
Please note that the Span has to be adapted as well; the calculation is not
done automatically.
TIME UNIT
12
For flowrate calculations, a time unit can be set. The flowrate can be
calculated per second (SEC), minute (MIN), hour (HR) or day (DAY).
Do select “------“ if no time is desired.
DECIMALS
13
This setting determines the number of digits following the decimal point.
The following can be selected:
000000 - 11111.1 - 222.22 - 33.333 - 4.4444 - .55555
Continued next page >>>