MODBUS-REGISTERS: DISPLAY
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 64
[h] 0x040
40065
display function
1
R/W
uint16 0=total
1=flowrate
2=acc.total
[d] 65
[h] 0x041
40066
show A-B
1
R/W
uint16 0=disable
1=enable
[d] 2147
[h] 0x863
42148
day totals
1
R/W
uint16 0=hidden
1=operate
2=off
[d] 80
[h] 0x050
40081
LCD update
time
1
R/W
uint16 0=fast
1=1sec
2=3sec
3=15sec
4=30sec
5=off
[d] 67
[h] 0x043
40068
backlight
brightness
1
R/W
uint16 0=off
1=20%
2=40%
3=60%
4=80%
5=100%
[d] 58
[h] 0x03A
40059
bar graph
enable
1
R/W
uint16 0=disable
1=absolute
2=rate A
3=rate B
[d] 59
[h] 0x03B
40060
bar graph range
2
R/W
uint32 0…9999999
Representation: unit, time, decimals depending on variables
48, 49, 50
MODBUS-REGISTERS: FLOWMETER
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 96
[h] 0x060
40097
flowmeter signal
- A
1
R/W
uint16 0=NPN
1=NPN LP
2=reed
3=reed LP
4=PNP
5=PNP LP
6=Namur
7=coil hi
8=coil lo
9=act 8.2V
10=act 24V
[d] 97
[h] 0x061
40098
flowmeter signal
- B
1
R/W
uint16 0=NPN
1=NPN LP
2=reed
3=reed LP
4=PNP
5=PNP LP
6=Namur
7=coil hi
8=coil lo
9=act 8.2V
10=act 24V
[d] 207
[h] 0x0CF
40208
bi-directional
1
R/W
uint16 0=disable
1=90°
2=270°
[d] 140
[h] 0x08C
40141
calculate
1
R/W
uint16 0=differ
1=add
2=not
negative
[d] 254
[h] 0x0FE
40255
K-factor
1
R/W
uint16 0=single
1=dual
[d] 1051
[h] 0x41B
41052
K-factor unit
type
1
R/W
uint16 0=hand
1=volumetric
2=mass
[d] 1050
[h] 0x41A
41051
K-factor unit
1
R/W
uint16 0=none
1=L
2=m
3
3=US GAL
4=I GAL
5=CF
6=OilBBL
7=kg
8=ton
9=LB
10=US ton
[d] 1046
[h] 0x416
41047
K-factor - A
2
R/W
uint32 1…9999999
Representation: 0.000010…9999999 depending on variable
1049: decimals K-factor A
[d] 1049
[h] 0x419
41050
K-factor - A
decimals
1
R/W
uint16 0…6
[d] 1062
[h] 0x426
41063
K-factor - B
2
R/W
uint32 1…9999999
Representation: 0.000010…9999999 depending on variable
1065: decimals K-factor B
[d] 1065
[h] 0x429
41066
K-factor - B
decimals
1
R/W
uint16 0…6
MODBUS-REGISTERS: ANALOG OUTPUT
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 112
[h] 0x070
40113
analog output
1
R/W
uint16 0=disable
1=enable
[d] 113
[h] 0x071
40114
minimum rate
2
R/W
uint32 0…9999999
Sign indicated by variable 125. Representation: unit, time,
decimals depending on variables 48, 49, 50
[d] 125
[h] 0x07D
40126
sign for
minimum rate
1
R/W
uint16 0=+ (positive) 1=- (negative)