background image

17

 

 

 

 
 
 

 

4.USAGE  AND  OPERATION 

 

 

Frequency conversion board fault table:

 

 

 

Protection/fault

 

Fault

 

display

 

Reason

 

Elimination methods

 

 

Drv1 MOP alarm

 

F01

 

MOP drive alarm

 

Recovery after the 150s

 

 

Inverter offline

 

F02

 

Frequency conversion board and main 
board communication failure

 

Check the communication connection

 

 

IPM protection

 

F03

 

IPM modular protection

 

Recovery after the 150s

 

 

Comp. Driver Failure

 

F04

 

Lack of phase, step or drive hardware 

damag

 

Check the measuring voltage check

 

requency conversion board hardware

 

 

DC Fan Fault

 

F05

 

Motor current feedback open circuit or 
short circuit

 

Check whether current return wires 

connected motor

 

 

IPM Overcurrent

 

F06

 

IPM Input current is large

 

Check and adjust the current 

measurement

 

Inv. DC Overvoltage

 

F07

 

DC bus voltage>Dc bus over-voltage 

protection value

 

Check the input voltage measurement

 

Inv. DC Lessvoltage

 

F08

 

DC bus voltage<Dc bus over-voltage 

protection value

 

Check the input voltage measurement

 

Inv. Input Lessvolt.

 

F09

 

The input voltage is low, causing the 

input current is high

 

Check the input voltage measurement

 

Inv. Input Overvolt.

 

F10

 

The input voltage is too high, more than 

outage protection current RMS

 

Check the input voltage measurement

 

Inv. Sampling Volt.

 

F11

 

The input voltage sampling fault

 

Check and adjust the current 

measurement

 

Comm. Err DSP-PFC

 

F12

 

DSP and PFC connect fault

 

Check the communication connection

 

Input Over Cur.

 

F26

 

The equipment load is too large

 

 

PFC fault

 

F27

 

The PFC circuit protection

 

Check the PFC switch tube 

short circuit 

or not

 

IPM Over heating

 

F15

 

The IPM module is overheat

 

Check and adjust the current 

measurement

 

eak Magnetic 

arn

 

F16

 

Compressor magnetic force is not 

enough

 

 

Inv. Input Out Phase

 

F17

 

The input voltage lost phase

 

Check and measure the voltage 

adjustment

 

IPM Sampling Cur.

 

F18

 

IPM sampling electricity is fault

 

Check and adjust the current 

measurement

 

Inv. Temp. Probe Fail

 

F19

 

Sensor is short circuit or open circuit

 

Inspect and replace the sensor

 

Inverter Overheating

 

F20

 

The transducer is overheat

 

Check and adjust the current 

measurement

 

Inv. Overheating 

arn

 

F22

 

Transducer temperature is too high

 

Check and adjust the current 

measurement

 

Comp. OverCur. 

arn

 

F23

 

Compressor electricity is large

 

The compressor over-current 

protection

 

Input Over Cur. 

arn

 

F24

 

Input current is too large

 

Check and adjust the current 

measurement

 

EEPROM Error 

arn

 

F25

 

MCU error

 

Check whether the chip is damaged 

Replace the chip

 

V15V over/undervoltage fault

 

F28

 

The V15V is overload or undervoltage

 

Check the V15V input voltage in range 

13.5v~16.5v or not

 

Summary of Contents for Astral Pool IHPt127

Page 1: ...ldren or infrm persons without supervision Please ensure that 3 08 2017 INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS Top Discharge Inverter Heat Pumps TOP DISCHARGE INVERTERHEATPUMPS Installation Instruction manual ...

Page 2: ......

Page 3: ...l Heat Pumps Location 5 3 3 How Close to Your Pool 5 3 4 Swimming Pool Heat Pumps Plumbing 6 3 5 Swimming Pool Heat Pumps Electrical Wiring 7 3 6 Initial Start up of the Unit 7 4 Usage and Operation 8 4 1 Color screen wire controller interface introduction 8 4 2 Color screen wire controller function introduction 9 4 3 Parameter list and breakdown table 16 4 4 Interface drawin 18 5 Maintenance and ...

Page 4: ...ccording to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has follo...

Page 5: ...acity Air 10 Water 26 Humid 64 Heating Capacity kW 1 9 8 0 2 6 10 8 4 3 18 2 Heating Capacity Btu 6460 27200 8840 36720 14552 61880 Consumed power kW 0 33 1 95 0 45 2 64 0 74 4 35 COP 4 10 5 76 4 1 5 78 4 18 5 78 Power Supply 230V 1P 50Hz 230V 1P 50Hz 230V 1P 50Hz Casing type ABS Fan Quantity 1 Fan Power Input W 200 200 200 Fan Speed RPM 500 700 500 700 600 800 Sound Pressure 1m dB A 42 54 42 56 4...

Page 6: ...200 120 IHPt127 IHPt168 IHPt246 Dimensions L W H mm 723 835 865 723 835 865 770 990 970 2 50 87 ...

Page 7: ...he inlet and outlet are clearly marked Water connections supplied are for 50mm PVC glue in plumbing All automatic sanitising devices must be installed after the heater and in such a way that the sanitiser cannot enter the heater without first mixing with the water in the pool or spa Sanitisers that are connected prior to the heater will void heaterwarranty The Astral Pool Heat Pump Pool Heater is ...

Page 8: ......

Page 9: ...40mm ...

Page 10: ...3 6 Initial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is completed you should follow these steps 1 Turn on your filter pump Check for water leaks and verify flow to and from the pool 2 Turn on the electrical power supply to the unit then press the key ON ...

Page 11: ...button Parameter Click this button to view the unit state and the parameter CLOCK Press to set the clock the timer on or timer off Fault display Click to view fault history Silent setting Click to turn on off silent function and to set timingLow speed function MODE Click to enter the mode switch interface Water Inlet Temp Click to enter mode setting and the target temp Setting interface 9 Temp cur...

Page 12: ...ting 2 2 1 Mode switch In the main interface click mode button or inlet water temperature setting button interface displays as follows Click the refrigeration mode button automatic mode button or heating mode button then you can select the corresponding mode Note when the unit is designed for single automatic mode or single thermal mode the mode can not be switched 2 2 2Target temp setting Clice t...

Page 13: ...on the time Settings button interface displays as follows Click the value to set time directly the click confirm button to save the Settings For example setup time the 30 11 2016 16 00 00 input 30 11 16 16 00 00 the time change then click confirm button Note if the input format is not correct the wrong time will be saved by clicking confirm button ...

Page 14: ...Click this button to start or end timing start setting function Timing on setting Click to set start time of the timing Timing end button Open red End gray Click this button to start or end timing end setting function Timing off setting Click to set end time of the timing For example above without action 0 o clock and 1o clock will be the on and off time of timing settings ...

Page 15: ... timing setting Click the silent setting button and the interface displays as follows 2 4 1 The silent button Click the silent button the unit will enter the silent mode and interface displays as follows Click the silent button again to exit the silent mode ...

Page 16: ...ent start time Click this button to set the timing silent start time Timing silent end time Click this button to set the timing silent end time Start time and end time setting value must be among the range of 0 00 23 00 and setting value can be precise to hour digit For example above click ON to use timing silent the unit will start the silent at 0 00 points and end at 4 00 click OFF to unuse the ...

Page 17: ... themain interface will display static if you check the failurerecord the main interface will displays static Failure record is in reverse order according to the happening time Press the Clean key you can delete the fault record 4 2 6 Color Display Calibration Keep click quickly at the blank area on any interface till you hear a long beep Then you will enter the calibration interface Click to star...

Page 18: ...perature recording curve is as follows 2 7 2 Comp Frequency curve Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest curve saved time if power is off and curve data collecting time is less than one hour the data in this period will not be saved ...

Page 19: ...n water system Check the pipe water flow and water pump Anti freezing Prot E07 Water flow is not enough Check the pipe water flow and whether water system is jammed or not Primary Anti freezing Prot E19 The ambient temp Is low Secondary Anti freezing Prot E29 The ambient temp Is low Water inlet and outlet temp E06 Water flow is not enough and low differential pressure Check the pipe water flow and...

Page 20: ...voltage measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication connection Input Over Cur F26 The equipment load is too large PFC fault F27 The PFC circuit protection Check the PFC switch tube short circuit or not IPM Over heating F15 The IPM module is overheat Check and adjus...

Page 21: ...1 12V GND 485_B2 485_A2 12V 12V 485_A3 485_B3 GND 12V 5V 0 10V OUT PWM OUT PWM IN 0 5V IN AI12 50K AI DI11 AI DI10 AI DI09 AI DI08 AI DI07 AI DI06 AI DI05 AI DI04 AI DI03 AI DI02 AI DI01 GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND T 5AL 250V ...

Page 22: ......

Page 23: ...xchange as conserve energy The operation pressure of the refrigerant system should only be serviced by a certified technician Check the power supply and cable connection often Should the unit begin to operate abnormally switch it off and contact the qualified technician Discharge all water in the water pump and water system so that freezing of the water in the pump or water system does not occur Y...

Page 24: ... RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices 7 The unit CANNOT be installed near the flammable gas Once there is any leakage of the gas fire can be occur 8 Make sure that there is circuit breaker for the unit lack of circuit breaker can lead to electrical shock or fire 9 The heat pump loc...

Page 25: ...50A 30mA less than 0 1 sec 186 224A 2x95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3x1 5mm2 1 5mm2 20A 30mA less than 0 1 sec nx0 5mm2 10 16A 3x2 5mm2 2 5mm2 32A 30mA less than 0 1 sec 16 25A 3x4mm2 4mm2 40A 30mA less than 0 1 sec 25 32A 3x6mm2 6mm2 40A 30mA less than 0 1 sec 32 40A 3x...

Page 26: ...Note ...

Page 27: ......

Page 28: ...20000 231607 sales fluidra com www astralpool com au Fluidra Group Australia Pty Ltd 219 Woodpark Road Smithfield N S W 2164 ABN 87 002 641 965 ...

Reviews: