7
Operational Malfunctions
Faultfinding list for troubleshooting
Operation
Application in conjunction with level electrode NRG ... in steam and (pressurized) hot water boilers
in accordance with TRD 40, TRD 60, TRD 604, EN 95, EN 95 or in accordance with national
regulations, and in conjunction with level electrodes NRG 6S, NRG 68S, NRG 69S for steam
boilers in marine applications.
Lowlevel limiter
Note
For troubleshooting consult section “Operational Malfunctions” on pages 7/8.
If faults occur that are not listed above, please contact our Technical Services or agency in your country.
Electrode submerged – lowlevel alarm
Fault:
The level switch indicates a lowlevel alarm before the level in the boiler has fallen below
the low level mark.
Remedy:
Check length of electrode tip. Measure the conductivity of the process or boiler water and
compare the values obtained with the marking on the name plate. Check correct wiring of
level switch and electrode in accordance with wiring diagram,
Fig. 10, Fig. 11
.
Fault:
After raising the water level above the lowlevel mark, the two red LEDs
0
are not
extinguished or only after quite a considerable period.
Remedy:
Check whether a vent hole has been provided in the protection tube. If the electrode is
fitted in a measuring pot outside the boiler, check position of isolating valves.
Fault:
One or both red LEDs
0
light up without the level having fallen below the lowlevel mark.
Remedy:
This means electronic failure within the level switch, i. e. failure of one or two of the
channels. Replace level switch.
Lowlevel reached – no function
Fault:
The water level falls below the lowlevel mark but neither of the two red LEDs
0
lights
up.
Remedy:
Check whether a vent hole has been provided in the protection tube. If the electrode is
fitted in a measuring pot outside the boiler, check position of isolating valves.
Fault:
The testing with the switch “TEST / INSPECTION”
9
was not successful, i. e. only one
red LED
0
or none of the two lighted up at the latest two minutes after the start of the
test.
Remedy:
Replace level switch.
EN
EN
Summary of Contents for NRS 1-7
Page 2: ... ...
Page 3: ... Deutsch Seite 4 21 English Page 22 39 DE EN ...
Page 10: ...10 Technische Daten Fortsetzung Maße Fig 2 106 7 32 51 Fig 3 112 85 DE ...
Page 11: ...11 Aufbau Fig 6 7 2 3 6 5 4 Fig 4 Fig 5 1 1 NRS 1 7 DE ...
Page 12: ...12 Funktionselemente NRS 1 7 Fig 7 9 0 MAX 55 C MAX 95 IP 65 DE ...
Page 15: ...15 Einbau Fortsetzung Einbaubeispiele 4 2 5 8 6 6 3 1 Fig 9 Fig 8 7 7 DE ...
Page 28: ...28 Technical Data continued Dimensions Fig 2 106 7 32 51 Fig 3 112 85 EN ...
Page 29: ...29 Design NRS 1 7 Fig 6 7 2 3 6 5 4 Fig 4 Fig 5 1 1 EN ...
Page 30: ...30 Functional Elements NRS 1 7 Fig 7 9 0 MAX 55 C MAX 95 IP 65 EN ...
Page 33: ...33 4 2 5 8 6 6 3 1 Installation continued Fig 9 Fig 8 Examples of Installation 7 7 EN ...