Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
22
Table 4.16 – Possible values of DI_Actuator_Faults_1_Chan
Value
Definition
0x01
Monitor Relay
0x02
Valve Jammed
0x04
Manual Moved
0x08
Over Torque
0x10
Phase Error
0x20
Motor Over Temperature
0x03
Monitor Relay + Valve Jammed
0x05
Monitor Relay + Manual Moved
0x09
Monitor Relay + Over Torque
0x11
Monitor Relay + Phase Error
0x21
Monitor Relay + Motor Over
Temperature
0x07
Monitor Relay + Valve
Manual Moved
0x13
Monitor Relay + Valve
Phase Error
0x23
Monitor Relay + Valve Jammed
Motor Over Temperature
4.2.4 DI_Actuator_Faults_2_Chan
Table 4.17
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Close
Torque
Switch Fault
Open Torque
Switch Fault
Manual
Moved
Valve
Jammed
Phase Error Thermal
Overload
Table 4.18 – Possible values of DI_Actuator_Faults_2_Chan
Value
Definition
0x01
Thermal Overload
0x02
Phase Error
0x04
Valve Jammed
0x08
Manual Moved
0x10
Open Torque Switch Fault
0x20
Close Torque Switch Fault
0x03
Thermal Ov Phase Error
0x05
Thermal Ov Valve Jammed
0x09
Thermal Ov Manual Moved
0x18
Manual Moved + Open Torque Switch Fault
0x28
Manual Moved + Close Torque Switch Fault
4.2.5 DI_Actuator_Alarms_Chan
Table 4.19
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Move Test
Active*
Not in
Remote
Close Inhibit
Active
Open Inhibit
Active
Remote ESD
Active
Local ESD
Active
* Available with Revision 1 to DeviceNet board.