LTQ008 – LTQ230 Series 3-Phase
Products
User Instructions –
AIIOM000165
EN
Page
38
of
40
9.5
Wire Sizing
Wire sizing data is provided in Table below to assist in the selection of the proper wire size for LTQ008 Series
actuators using various wire sizes over distance. Always reference the correct voltage, and do not exceed the
indicated length of the wire run for each model.
Table 5: Maximum distance between actuator and power supply
LTQ008-LTQ017
ACTUATOR
Voltage
230 / 3
380 / 3
480 / 3
575 / 3
Amps
0.7
0.4
0.2
0.2
AWG
Maximum Distance – Actuator to Power Supply (ft)
16
1665
10752
25636
33559
14
2649
17102
40774
53375
12
4212
27193
64833
84869
10
6695
43225
103058
134908
8
10650
68761
163940
214606