7.3
Calibration Procedure for BIC + LL Control Station Proportional Control
After completing all mounting and wiring procedures, and main power is available, it is now possible to
commission the actuator.
1.
Position the actuator to a mid-stroke position.
2.
Apply correct power according to the actuator model.
3.
Press the S1 button on the control board for 5 seconds, the blue light (D18) turnsthe
red light (D3) turns off. The system then enters the stroke setting mode.
4.
First, set the full CW stroke position.
a.
Under the full CW setting mode, press S3 button for the actuator to
move CW.
b.
Press S3 to move CW until the actuator reaches full CW position and
then release the button.
c.
Press S1 button for 5 seconds, the blue light (D18) and red light (D3)
both turn on.
d.
The MCU will record the CW (0%) position, and then enters the full
CCW setting mode.
5.
Set the full CCW stroke position.
a.
Press S2 button for the actuator to move CCW.
b.
Continue to pressing S2 towards 100% until the actuator reaches full
CCW position and then release the button to stop.
c.
Press S1 button for 5 seconds, blue light (D3) turns off and the red light
(D3) turns on.
d.
The MCU will record the CCW (100%) position.
6.
Setting is done.
7.
Note: The actuator has a blocked protection function. When stroke block occurs for over 10 seconds, the
system goes into lock mode and stops the stroke movement. If it happens during the stroke setting, move
the stroke towards the opposite direction to unlock. For example if it happens at 0% position, direct the
stroke towards 100% to release the block protection.
8.
On/Off Control stops here, Calibration is complete.