Installation

3

Motor

Minimum

Switch Setting

Full Load 

Circuit Required

Model

HP

Amps

RPM

(Amps)

On                   Off

FPPS5700A

3/4

9.5

3450

15

13-1/2 (33, 7cm)    6-3/4 (17, 2cm)         

ELECTRICAL AND SWITCH SPECIFICATIONS

GPH (LPH) of Water @ Total Feet (Meters) of Lift

Maximum

Model

HP

5’ (1, 5)

10’ (3)

15’ (4, 6)

20’ (6, 1)

Lift

FPPS5700A

3/4

5280 (19 986)

4800 (18 169)

4600 (17 412)

3720 (14 081)

42’ (12, 8)

PERFORMANCE

INSTALLATION

1. Install pumps in sump pit with minimum diameter of 14".

Sump depth should be 18". Construct sump pit of tile, 
concrete, steel, or plastic. Check local codes for approved
materials.

2. Install pump in pit so that switch operating mechanism has

maximum possible clearance.

3. Pump should not be installed on clay, earth, or sand

surfaces. Clean sump pit of small stones and gravel which
could clog pump. Keep pump inlet screen clear.

NOTE: 

Do not use ordinary pipe joint compound on plastic

pipe. Pipe joint compound can attack plastics.

4. Install discharge plumbing. Use rigid plastic pipe and wrap

threads with Teflon tape or use Plasto Joint Stik

1

. Screw pipe

into pump hand tight +1-1⁄2 turns.

Risk of flooding. If a flexible discharge hose is

used, make sure pump is secured in sump to prevent
movement. 

Failure to secure pump may allow pump

movement, switch interference, and prevent pump from
starting or stopping.

5. To reduce motor noise and vibrations, a short length of

rubber hose (1-7/8" I.D., e.g. radiator hose) can be
connected into discharge line near pump using suitable
clamps.

6. Install an in-line check valve to prevent flow backwards

through pump when pump shuts off.

7. Power Supply: Pump is designed for 115 V., 60 Hz.,

operation and requires a minimum 15 amp dedicated
circuit. Both pump and switch are supplied with 3-wire
cord sets with grounding-type plugs. For automatic
operation, switch plug is inserted directly into outlet and
pump plug inserts into opposite end of switch plug. For
manual operation, pump plug is inserted directly into
outlet.

Pump should always be electrically grounded

to a suitable electrical ground such as a grounded water pipe
or a properly grounded metallic raceway, or ground wire
system. Do not cut off round ground pin.

8. If pump discharge line is exposed to sub-freezing

temperature, portion of line exposed must be installed so

any water remaining in pipe will drain to the outfall by
gravity. Failure to do this can cause water trapped in
discharge to freeze, which could result in damage to
pump.

9. After piping and check valve have been installed, unit is

ready for operation.

10. Check operation by filling sump with water and observing

pump operation through one complete cycle.

Failure to make this operational check may lead to improper
operation, premature failure, and flooding.

1

Lake Chemical Co., Chicago, Illinois

OPERATION

Risk of electric shock. Do not handle a pump

or pump motor with wet hands or when standing on wet or
damp surface, or in water.

1. Shaft seal depends on water for lubrication. Do not operate

pump unless it is submerged in water as seal may be
damaged if allowed to run dry.

2. Motor is equipped with automatic reset thermal protector. If

temperature in motor should rise unduly, switch will cut off
all power before damage can be done to motor. When
motor has cooled sufficiently, switch will reset automatically
and restart motor. If protector trips repeatedly, pump should
be removed and checked as to cause of difficulty. Low
voltage, long extension cords, clogged impeller, very low
head or lift, etc., could cause cycling.

3. Pump will not remove all water. If manually operated pump

is operating and suddenly no water comes out discharge
hose, shut OFF unit immediately. Water level is probably
very low and unit has broken prime.

Risk of electric shock. Before attempting to

check why unit has stopped operating, disconnect power from
unit. Do not handle pump with wet hands or  when standing
on wet or damp surfaces, or in water.

NOTE:

No repair parts available for this pump except a switch.

Replacement switches are designed for universal mounting on
the discharge pipe, not on the pump. Order Switch part
number 1000001334.

For parts or assistance, call Flotec Customer Service at 

1-800-365-6832

Summary of Contents for FPSS5700A

Page 1: ...l 1 800 365 6832 English Pages 2 5 Installation Fonctionnement Pi ces Pour plus de renseignements concernant l utilisation l installation ou l entretien Composer le 1 800 365 6832 Fran ais Pages 6 9 I...

Page 2: ...re each use making certain that all connections are secure Periodically inspect sump pump and system components Keep free of debris and foreign objects Perform routine maintenance as required Personal...

Page 3: ...rounded to a suitable electrical ground such as a grounded water pipe or a properly grounded metallic raceway or ground wire system Do not cut off round ground pin 8 If pump discharge line is exposed...

Page 4: ...of binding and clean out hose or remove 6 Float obstructed 6 Remove obstruction Pump starts and 1 Backflow of water from piping 1 Install or replace check valve stops too often 2 Faulty float switch 2...

Page 5: ...isapplication tampering alteration nor due to improper installation operation maintenance or storage nor to other than normal application use or service including but not limited to operational failur...

Page 6: ...ue les tuyaux souples ne comportent pas de points faibles ni de parties us es et que tous les raccords sont bien serr s P riodiquement inspecter la pompe et tous les l ments de l ensemble Proc der un...

Page 7: ...rancher la fiche de la pompe directement dans la prise de courant La pompe doit toujours tre raccord e la terre sur un tuyau d eau mis la terre une canalisation m tallique ad quatement mise la terre o...

Page 8: ...gager avec un tuyau ou l enlever 6 Flotteur obstru 6 Enlever l obstruction La pompe d marre 1 Circulation contre courant de 1 Poser un clapet de non retour ou le remplacer et s arr te l eau dans les t...

Page 9: ...duits qui n ont pas t install s utilis s entrepos s ou entretenus correctement ni ceux qui n ont pas t utilis s ou entretenus normalement y compris mais sans s y limiter aux produits ayant des pannes...

Page 10: ...conexiones est n firmes Inspeccione peri dicamente el sumidero la bomba y los componentes del sistema Mant ngala limpia de basuras y objetos extra os Realice el mantenimiento de rutina como sea neces...

Page 11: ...tierra en una masa el ctrica adecuada tal como una tuber a de agua conectada a tierra un conducto met lico debidamente puesto a tierra o un sistema de hilos de puesta a tierra No corte la clavija redo...

Page 12: ...a desde las tuber as 1 Instale o cambie la v lvula de retenci n se detiene con 2 Interruptor de flotador defectuoso 2 Cambie el interruptor demasiada frecuencia La bomba no 1 Interruptor de flotador d...

Page 13: ...o mantenimiento o almacenaje incorrectos ni a ninguna otra cosa que no sea su aplicaci n uso o servicio normales incluyendo pero no limitado a fallas operacionales causadas por corrosi n oxidaci n u o...

Page 14: ...14...

Page 15: ...15...

Page 16: ......

Reviews: