Flotec FP4000 Series Owner'S Manual Download Page 7

Electrical

 Risk of electric shock . Can shock, burn or kill. Connect ground 

wire before connecting power supply wires. Use the wire size (including 
the ground wire) specified in the wiring chart. If possible, connect the pump 
to a separate branch circuit with no other appliances on it.

 Risk of explosion . Do not ground to a gas supply line.

Wiring Connections

 Risk of fire . Incorrect voltage can cause a fire or seriously 

damage the motor and voids the warranty. The supply voltage must be 
within ±10% of the motor nameplate voltage.
NOTICE Dual-voltage motors may be set for 115 V or 230 V. If necessary, 
reset the motor to the desired voltage, as shown. Do not alter the wiring in 
single voltage motors. 
Install, ground, wire, and maintain your pump in compliance with the 
National Electrical Code (NEC) or the Canadian Electrical Code (CEC), as 
applicable, and with all local codes and ordinances that apply. Consult 
your local building inspector for code information.
Connection Procedure:
1. Connect the ground wire first as shown in Figure 6. The ground wire

must be a solid copper wire at least as large as the power supply wires.

2. There must be a solid metal connection between the pressure switch

and the motor for motor grounding protection. If the pressure switch
is not connected to the motor, connect the green ground screw in the
switch to the green ground screw under the motor end cover. Use a
solid copper wire at least as large as the power supply wires.

3. Connect the ground wire to a grounded lead in a service panel, to a

metal underground water pipe, to a metal well casing at least ten feet
(3 m) long, or to a ground electrode provided by the power company or
the hydro authority.

4. Connect the power supply wires to the pressure switch as shown in

Figure 6.

You have just completed the wiring for your pump.
Please go to Page 9 for startup preparations.

Wiring Chart – Recommended Wire and Fuse Sizes

Motor HP

Volts

Max . Load 

Amp

Branch Fuse 

Rating Amp

DISTANCE IN FEET FROM MOTOR TO SUPPLY

0 - 100 

101 - 200 

201 - 300 

301 - 400 

401 - 500

AWG WIRE SIZE (mm

2

)

1/2

115/230

9.9/4.95

15/15

14/14 (2/2)

14/14 (2/2)

12/14 (3/2)

10/14 (5.5/2)

10/12 (5.5/3)

3/4

115/230

14.8/7.4

20/15

12/14 (3/2)

8/14 (8.4/2)

6/14 (14/2)

6/12 (4/3)

4/10 (21/5.5)

1

115/230

19.2/9.6

25/15

10/14 (5.5/2)

8/14 (8.4/2)

6/12 (14/3)

4/10 (21/5.5)

4/10 (21/5.5)

Summary of Contents for FP4000 Series

Page 1: ...OWNER S MANUAL Shallow Well Jet Pumps Installation Operation Parts 2489 0696 558 0397 FP4000 FP4100 FP4800...

Page 2: ...terminals together Do not touch metal screwdriver blade or capacitor terminals If in doubt consult a qualified electrician General Safety Risk of burns Do not touch an operating motor Motors are desi...

Page 3: ...n port on the pump include a check valve if your pump is not equipped with one see Figure 1 Support the pipe so that there are no dips or sags in the pipe so it doesn t strain the pump body and so tha...

Page 4: ...lbows in the suction pipe The suction pipe should be at least as large as the suction port on the pump 2 Assemble a foot valve and suction pipe see Figure 3 Make sure that the foot valve works freely...

Page 5: ...pipe size must be at least as large as the discharge port 3 Install a tee in the suction pipe near the pump Install a reducer bushing down to 1 8 NPT in the tee Run tubing from the tee to the port on...

Page 6: ...sure switch as shown in Figure 8 4 Attach the ground wire to the grounding connections as shown in Figure 8 5 If there are other wires they should be capped 6 Reinstall the motor end and pressure swit...

Page 7: ...ust be a solid copper wire at least as large as the power supply wires 2 There must be a solid metal connection between the pressure switch and the motor for motor grounding protection If the pressure...

Page 8: ...at this several times in order to get all the trapped air out of the piping A pump lifting water 25 may take as long as 15 minutes to prime 4 After the pump begins building pressure in the system shut...

Page 9: ...valve and or strainer are buried in sand or mud Raise foot valve and or strainer above bottom of water source Clean foot valve and strainer Water level is too low for shallow well setup to deliver wa...

Page 10: ...ft Seal 1 U9 6 5 Impeller 1 J105 40PNB J105 42PNB 5A Floating Wear Ring 1 N23 12SS 6 Priming Baffle 1 U97 153P 7 Nozzle Venturi Diffuser Assembly 1 N101 30PA N101 30P 8 Nozzle O Ring 1 U9 449 9 Pump B...

Page 11: ...d Gasket Kit FPP1550 4 Pump Body Assembly N176 38 N176 38F 5 Overhaul Kit FPP1560 FPP1561 6 Pressure Switch TC2151 Includes Water slinger seal plate O Ring or gasket shaft seal and diffuser O Ring or...

Page 12: ...g 1 111P0500 6 Impeller 1 101P1720 101P1730 7 Venturi 1 101P2900 8 O Ring 1 111P1100 9 90 Hose Barb 1 171P4750T 10 Pump Body 1 723S0850 11 12 Plug Stainless Steel Washer 1 111P0990 13 Screw Socket Hea...

Reviews: