![Flomotion Systems 2001H Series Installation And Operation Manual Download Page 22](http://html1.mh-extra.com/html/flomotion-systems/2001h-series/2001h-series_installation-and-operation-manual_2306737022.webp)
2001 Peristaltic Pump O&M Manual
4.13 Factory Default / User Settings Record
* Controller has been programmed for 2001 Series Series Settings as shown below.
PARAMETER NAME: USER SETTINGS RECORD
Parameter
Number
Parameter
Name
Factory
Default
2001 Series
Series
Settings*
0
LINE VOLTS
AUTO
-
1
SPEED #1
20 Hz
25% HZ
2
SPEED #2
20 Hz
25% HZ
3
SPEED #3
20 Hz
25% HZ
4
SPEED #4
20 Hz
25% HZ
5
SKIP #1
.00 Hz
-
6
SKIP #2
.00 Hz
-
7
BAND WID
1.00 Hz
5 Hz
8
ACCEL
30.0 SEC
5 SEC
9
DECEL
30.0 SEC
5 SEC
10
MIN FRQ
.50 Hz
0 Hz
11
MAX FRQ
60.00
75 Hz
12
DC BRAKE
.0 VDC
-
13
DC TIME
.0 SEC
-
14
DYN BRAKE
OFF
-
16
CURRENT
180 %
-
17
MOTOR OL
100 %
-
18
BASE
60.00 Hz
-
19
FX BOOST
(Note 1)
5.3 %
22
TORQUE
CONSTANT
-
23
CARRIER
2.5 kHz
12 KHz
25
START
NORMAL
POWER UP
26
STOP
COAST
-
28
AUTO/MAN
A/M LOC
A/M SPD
30
CONTROL
LOCAL
REMOTE
31
UNITS
Sp HERTZ
% Hz
32
HZ MULT
1.00
-
33
UNITS DP
XXXXX
XXX.X
34
LOAD MLT
100 %
-
35
CONTRAST
HIGH
-
36
SLEEP TH
.00 Hz
2.0 Hz
37
SLEEP DL
30.0 SEC
5.0 SEC
38
SLEEP BW
0%
39
TB5 MIN
.00 Hz
0%Hz
40
TB5 MAX
60.00 Hz
100% Hz
41
AIN FLTR
0.02 SEC
0.02 SEC
42
TB10A OUT
NONE
-
43
@TB10A
60.00 Hz
NONE
44
TB10B OUT
NONE
-
45
@TB10B
125 %
-
47
TB13A
NONE
4-20 mA
48
TB13B
NONE
-
49
TB13C
NONE
-
50
TB13D
EXT FAULT
-
Flomotion Systems, Inc. 2001H SERIES
Pg. 22
Note that the % symbol
only appears if it is
selected in step 31.