26
3 CI600 main menu
3.1 Fan speeds
The main menu contains various choices. Most
concern fan speeds. The speed selected is
indicated with large fan symbols and bold font.
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
MAIN MENU
LANGUAGE
NORSK
ENGLISH
SVENSKA
DEUTCH
NEDERLANDS
SUOMI
DANSK
OK?
TIME AND DATE
13 : 45 04.07.09
FILTER
INTERVAL CHANGE OF FILTER
RESET FILTER ALARM
INTERVAL CHANGE OF FILTER
6 MND
TIMER
SCREENSAVER
DAY / WEEK SETTINGS
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
OK?
TEMPERATURE
18
HEATING ELEMENT ON/OFF
HEATING ELEMENT ON
OK?
60 min
13.08.2009
16:43
18°C 22°C
- NORMAL
START MENU
LANGUAGE
TIME AND DATE
MAIN MENU
OK?
START UP MENU
SETTINGS
MAIN MENU 1
SETTINGS
MAIN MENU 2
MAIN MENU 2
>
>
>
OK?
MIN
NORMAL
MAX
MAX TIMER
MAIN MENU
SETTINGS
>
MAIN MENU
SETTINGS
>
MIN
NORMAL
MAX
MAX TIMER
OK?
MIN
NORMAL
MAX
MAX TIMER
OK?
>
>
OK?
>
>
>
>
>
TEMPERATURE 1
TEMPERATURE 2
OK?
HEATING ELEMENT ON/OFF
TIMER
TIME AND DATE
LANGUAGES
FILTER 2
FILTER 1
DAY/WEEK SETTINGS 1
DAY/WEEK SETTINGS 2
OK?
°C
TIME DAY MONTH YEAR
>
OK?
OK?
>
OK?
ALARM
RESET ALARM
ALARM
OK?
PIN CODE
PIN CODE
OK?
0 0 0 0
ADVANCED USER
TEMPERATURE REGULATION
FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
ADVANCED USER
>
OK?
>
>
>
>
OPERATING INFORMATION
SET TEMPERATURE
DAY / WEEK SETTINGS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
HEAT RECOVERY SYSTEM
COOLING
HEATING
OPERATING INFORMATION
22°
AKTIV
22°
21°
0°
35°
100%
0%
100%
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
TEMPERATURE REGULATION
>
>
OK?
>
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
REGULATION TYPE 1
EXTR OK?
35°
15°
REGULATION TYPE
REGULATION
REGULATION TYPE 2
SUPPL OK?
COOLING
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
KJØLING
OK?
>
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
KJØLEGJENVINNING
NØYTRALSONE
AV
18°
MIN
180 s
OFF
1°
OK?
NEUTRAL ZONE
COOLNESS RECOVERY
HEAT RECOVERY SYSTEM
2°
1°
OK?
EXT. TEMP. CONTROL
EXT. TEMP. CONTROL
EXTERNAL TEMPERATURE CONTROL
OFF
OK?
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
FAN REGULATION
>
>
OK?
>
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
INLET AIR
OK?
50%
75%
100%
EXTRACT AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
EXTRACT AIR
OK?
50%
75%
100%
TIMER
STANDARD SPEED
STANDARD TIME
TIMER
OK?
MAX
30 m
AIR VOLUME COMPENSATION
SUPPLY AIR
EXTRACT AIR
AIR VOLUME COMPENSATION
OK?
MAX
MIN
CONFIGURATION
SENSORS
FIRE/SMOKE
COMMUNICATION
START/STOP SEQUENCE
REST MODE
CONFIGURATION
>
>
OK?
>
>
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
FILTER GUARD
SENSORS
>
>
OK?
>
>
SUPPLY AIR
CALIBRATION
INLET AIR
OK?
0
FILTER GUARD
ACTIVATION
PRESSURE GUARD
OK?
OFF
FIRE/SMOKE
MODE
FIRE/SMOKE
OK?
1
COMMUNICATION
HOME/AWAY
COMMUNICATION
OK?
HOME/AWAY
SPEED
TEMPERATURE
TIME DELAY
HOME/AWAY
OK?
MIN
18°
60 m
START/STOP SEQUENCE
START DELAY 1
START DELAY 2
START DELAY 3
START DELAY 4
STOP SEQUENCE EL
START/STOP SEQUENCE
OK?
0 s
20 s
20 s
20 s
180 s
REST MODE
SLEEP MODE
TIME DELAY
2 min OK?
OPERATING TIME
OPERATING TIME
OPERATING TIME
FILTER
312 tim
125 tim
TEST
FANS
HEATING
HEAT RECOVERY SYSTEM
COOLING
SENSORS
TEST
>
>
OK?
>
>
FANS
AC FANS
EC FANS
FANS
OK?
MIN
0%
HEATING
ACTIVATION
HEATING
OK?
OFF
HEAT RECOVERY SYSTEM
ACTIVATION
HEAT RECOVERY UNIT
OK?
OFF
COOLING
ACTIVATION
COOLING
OK?
OFF
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
TEMPERATURE SENSORS
22°
21°
0°
35°
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
OPERATING INFORMATION
MENU HANDLING 1
>
>
OK?
>
>
>
>
>
>
TIME AND DATE
13 : 45 04.07.09
MENU HANDLING 2
TIME DAY MONTH YEAR
OK?
TUESDAY
1
08
: 00 16 : 00
-
MIN
16°
2 16 : 00 18: 00
-
NORMAL
18°
3 18: 00 19 : 00
-
MAX
16°
4 19 : 00 24 : 00
-
NORMAL
18°
To change the speed, move the cursor with buttons
1 and 3. Then confirm your selection with button 4
and the speed selected is highlighted with large fan
symbols and bold font.
3.2 Settings
Under the SETTINGS menu item, you can adapt the
system as you want.
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
MAIN MENU
LANGUAGE
NORSK
ENGLISH
SVENSKA
DEUTCH
NEDERLANDS
SUOMI
DANSK
OK?
TIME AND DATE
13 : 45 04.07.09
FILTER
INTERVAL CHANGE OF FILTER
RESET FILTER ALARM
INTERVAL CHANGE OF FILTER
6 MND
TIMER
SCREENSAVER
DAY / WEEK SETTINGS
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
OK?
TEMPERATURE
18
HEATING ELEMENT ON/OFF
HEATING ELEMENT ON
OK?
60 min
13.08.2009
16:43
18°C 22°C
- NORMAL
START MENU
LANGUAGE
TIME AND DATE
MAIN MENU
OK?
START UP MENU
SETTINGS
MAIN MENU 1
SETTINGS
MAIN MENU 2
MAIN MENU 2
>
>
>
OK?
MIN
NORMAL
MAX
MAX TIMER
MAIN MENU
SETTINGS
>
MAIN MENU
SETTINGS
>
MIN
NORMAL
MAX
MAX TIMER
OK?
MIN
NORMAL
MAX
MAX TIMER
OK?
>
>
OK?
>
>
>
>
>
TEMPERATURE 1
TEMPERATURE 2
OK?
HEATING ELEMENT ON/OFF
TIMER
TIME AND DATE
LANGUAGES
FILTER 2
FILTER 1
DAY/WEEK SETTINGS 1
DAY/WEEK SETTINGS 2
OK?
°C
TIME DAY MONTH YEAR
>
OK?
OK?
>
OK?
ALARM
RESET ALARM
ALARM
OK?
PIN CODE
PIN CODE
OK?
0 0 0 0
ADVANCED USER
TEMPERATURE REGULATION
FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
ADVANCED USER
>
OK?
>
>
>
>
OPERATING INFORMATION
SET TEMPERATURE
DAY / WEEK SETTINGS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
HEAT RECOVERY SYSTEM
COOLING
HEATING
OPERATING INFORMATION
22°
AKTIV
22°
21°
0°
35°
100%
0%
100%
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
TEMPERATURE REGULATION
>
>
OK?
>
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
REGULATION TYPE 1
EXTR OK?
35°
15°
REGULATION TYPE
REGULATION
REGULATION TYPE 2
SUPPL OK?
COOLING
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
KJØLING
OK?
>
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
KJØLEGJENVINNING
NØYTRALSONE
AV
18°
MIN
180 s
OFF
1°
OK?
NEUTRAL ZONE
COOLNESS RECOVERY
HEAT RECOVERY SYSTEM
2°
1°
OK?
EXT. TEMP. CONTROL
EXT. TEMP. CONTROL
EXTERNAL TEMPERATURE CONTROL
OFF
OK?
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
FAN REGULATION
>
>
OK?
>
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
INLET AIR
OK?
50%
75%
100%
EXTRACT AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
EXTRACT AIR
OK?
50%
75%
100%
TIMER
STANDARD SPEED
STANDARD TIME
TIMER
OK?
MAX
30 m
AIR VOLUME COMPENSATION
SUPPLY AIR
EXTRACT AIR
AIR VOLUME COMPENSATION
OK?
MAX
MIN
CONFIGURATION
SENSORS
FIRE/SMOKE
COMMUNICATION
START/STOP SEQUENCE
REST MODE
CONFIGURATION
>
>
OK?
>
>
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
FILTER GUARD
SENSORS
>
>
OK?
>
>
SUPPLY AIR
CALIBRATION
INLET AIR
OK?
0
FILTER GUARD
ACTIVATION
PRESSURE GUARD
OK?
OFF
FIRE/SMOKE
MODE
FIRE/SMOKE
OK?
1
COMMUNICATION
HOME/AWAY
COMMUNICATION
OK?
HOME/AWAY
SPEED
TEMPERATURE
TIME DELAY
HOME/AWAY
OK?
MIN
18°
60 m
START/STOP SEQUENCE
START DELAY 1
START DELAY 2
START DELAY 3
START DELAY 4
STOP SEQUENCE EL
START/STOP SEQUENCE
OK?
0 s
20 s
20 s
20 s
180 s
REST MODE
SLEEP MODE
TIME DELAY
2 min OK?
OPERATING TIME
OPERATING TIME
OPERATING TIME
FILTER
312 tim
125 tim
TEST
FANS
HEATING
HEAT RECOVERY SYSTEM
COOLING
SENSORS
TEST
>
>
OK?
>
>
FANS
AC FANS
EC FANS
FANS
OK?
MIN
0%
HEATING
ACTIVATION
HEATING
OK?
OFF
HEAT RECOVERY SYSTEM
ACTIVATION
HEAT RECOVERY UNIT
OK?
OFF
COOLING
ACTIVATION
COOLING
OK?
OFF
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
TEMPERATURE SENSORS
22°
21°
0°
35°
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
OPERATING INFORMATION
MENU HANDLING 1
>
>
OK?
>
>
>
>
>
>
TIME AND DATE
13 : 45 04.07.09
MENU HANDLING 2
TIME DAY MONTH YEAR
OK?
TUESDAY
1
08
: 00 16 : 00
-
MIN
16°
2 16 : 00 18: 00
-
NORMAL
18°
3 18: 00 19 : 00
-
MAX
16°
4 19 : 00 24 : 00
-
NORMAL
18°
3.3 Temperature
Here you set the temperature for the air that
enters the building.
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
MAIN MENU
LANGUAGE
NORSK
ENGLISH
SVENSKA
DEUTCH
NEDERLANDS
SUOMI
DANSK
OK?
TIME AND DATE
13 : 45 04.07.09
FILTER
INTERVAL CHANGE OF FILTER
RESET FILTER ALARM
INTERVAL CHANGE OF FILTER
6 MND
TIMER
SCREENSAVER
DAY / WEEK SETTINGS
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
OK?
TEMPERATURE
18
HEATING ELEMENT ON/OFF
HEATING ELEMENT ON
OK?
60 min
13.08.2009
16:43
18°C 22°C
- NORMAL
START MENU
LANGUAGE
TIME AND DATE
MAIN MENU
OK?
START UP MENU
SETTINGS
MAIN MENU 1
SETTINGS
MAIN MENU 2
MAIN MENU 2
>
>
>
OK?
MIN
NORMAL
MAX
MAX TIMER
MAIN MENU
SETTINGS
>
MAIN MENU
SETTINGS
>
MIN
NORMAL
MAX
MAX TIMER
OK?
MIN
NORMAL
MAX
MAX TIMER
OK?
>
>
OK?
>
>
>
>
>
TEMPERATURE 1
TEMPERATURE 2
OK?
HEATING ELEMENT ON/OFF
TIMER
TIME AND DATE
LANGUAGES
FILTER 2
FILTER 1
DAY/WEEK SETTINGS 1
DAY/WEEK SETTINGS 2
OK?
°C
TIME DAY MONTH YEAR
>
OK?
OK?
>
OK?
ALARM
RESET ALARM
ALARM
OK?
PIN CODE
PIN CODE
OK?
0 0 0 0
ADVANCED USER
TEMPERATURE REGULATION
FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
ADVANCED USER
>
OK?
>
>
>
>
OPERATING INFORMATION
SET TEMPERATURE
DAY / WEEK SETTINGS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
HEAT RECOVERY SYSTEM
COOLING
HEATING
OPERATING INFORMATION
22°
AKTIV
22°
21°
0°
35°
100%
0%
100%
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
TEMPERATURE REGULATION
>
>
OK?
>
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
REGULATION TYPE 1
EXTR OK?
35°
15°
REGULATION TYPE
REGULATION
REGULATION TYPE 2
SUPPL OK?
COOLING
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
KJØLING
OK?
>
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
KJØLEGJENVINNING
NØYTRALSONE
AV
18°
MIN
180 s
OFF
1°
OK?
NEUTRAL ZONE
COOLNESS RECOVERY
HEAT RECOVERY SYSTEM
2°
1°
OK?
EXT. TEMP. CONTROL
EXT. TEMP. CONTROL
EXTERNAL TEMPERATURE CONTROL
OFF
OK?
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
FAN REGULATION
>
>
OK?
>
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
INLET AIR
OK?
50%
75%
100%
EXTRACT AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
EXTRACT AIR
OK?
50%
75%
100%
TIMER
STANDARD SPEED
STANDARD TIME
TIMER
OK?
MAX
30 m
AIR VOLUME COMPENSATION
SUPPLY AIR
EXTRACT AIR
AIR VOLUME COMPENSATION
OK?
MAX
MIN
CONFIGURATION
SENSORS
FIRE/SMOKE
COMMUNICATION
START/STOP SEQUENCE
REST MODE
CONFIGURATION
>
>
OK?
>
>
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
FILTER GUARD
SENSORS
>
>
OK?
>
>
SUPPLY AIR
CALIBRATION
INLET AIR
OK?
0
FILTER GUARD
ACTIVATION
PRESSURE GUARD
OK?
OFF
FIRE/SMOKE
MODE
FIRE/SMOKE
OK?
1
COMMUNICATION
HOME/AWAY
COMMUNICATION
OK?
HOME/AWAY
SPEED
TEMPERATURE
TIME DELAY
HOME/AWAY
OK?
MIN
18°
60 m
START/STOP SEQUENCE
START DELAY 1
START DELAY 2
START DELAY 3
START DELAY 4
STOP SEQUENCE EL
START/STOP SEQUENCE
OK?
0 s
20 s
20 s
20 s
180 s
REST MODE
SLEEP MODE
TIME DELAY
2 min OK?
OPERATING TIME
OPERATING TIME
OPERATING TIME
FILTER
312 tim
125 tim
TEST
FANS
HEATING
HEAT RECOVERY SYSTEM
COOLING
SENSORS
TEST
>
>
OK?
>
>
FANS
AC FANS
EC FANS
FANS
OK?
MIN
0%
HEATING
ACTIVATION
HEATING
OK?
OFF
HEAT RECOVERY SYSTEM
ACTIVATION
HEAT RECOVERY UNIT
OK?
OFF
COOLING
ACTIVATION
COOLING
OK?
OFF
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
TEMPERATURE SENSORS
22°
21°
0°
35°
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
OPERATING INFORMATION
MENU HANDLING 1
>
>
OK?
>
>
>
>
>
>
TIME AND DATE
13 : 45 04.07.09
MENU HANDLING 2
TIME DAY MONTH YEAR
OK?
TUESDAY
1
08
: 00 16 : 00
-
MIN
16°
2 16 : 00 18: 00
-
NORMAL
18°
3 18: 00 19 : 00
-
MAX
16°
4 19 : 00 24 : 00
-
NORMAL
18°
We recommend adjusting the temperature to max
18° so that the air is mixed optimally with the air
already in the building.
3.4 Daily/weekly timer
The programming of the timer begins by selecting
the day.
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
MAIN MENU
LANGUAGE
NORSK
ENGLISH
SVENSKA
DEUTCH
NEDERLANDS
SUOMI
DANSK
OK?
TIME AND DATE
13 : 45 04.07.09
FILTER
INTERVAL CHANGE OF FILTER
RESET FILTER ALARM
INTERVAL CHANGE OF FILTER
6 MND
TIMER
SCREENSAVER
DAY / WEEK SETTINGS
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
OK?
TEMPERATURE
18
HEATING ELEMENT ON/OFF
HEATING ELEMENT ON
OK?
60 min
13.08.2009
16:43
18°C 22°C
- NORMAL
START MENU
LANGUAGE
TIME AND DATE
MAIN MENU
OK?
START UP MENU
SETTINGS
MAIN MENU 1
SETTINGS
MAIN MENU 2
MAIN MENU 2
>
>
>
OK?
MIN
NORMAL
MAX
MAX TIMER
MAIN MENU
SETTINGS
>
MAIN MENU
SETTINGS
>
MIN
NORMAL
MAX
MAX TIMER
OK?
MIN
NORMAL
MAX
MAX TIMER
OK?
>
>
OK?
>
>
>
>
>
TEMPERATURE 1
TEMPERATURE 2
OK?
HEATING ELEMENT ON/OFF
TIMER
TIME AND DATE
LANGUAGES
FILTER 2
FILTER 1
DAY/WEEK SETTINGS 1
DAY/WEEK SETTINGS 2
OK?
°C
TIME DAY MONTH YEAR
>
OK?
OK?
>
OK?
ALARM
RESET ALARM
ALARM
OK?
PIN CODE
PIN CODE
OK?
0 0 0 0
ADVANCED USER
TEMPERATURE REGULATION
FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
ADVANCED USER
>
OK?
>
>
>
>
OPERATING INFORMATION
SET TEMPERATURE
DAY / WEEK SETTINGS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
HEAT RECOVERY SYSTEM
COOLING
HEATING
OPERATING INFORMATION
22°
AKTIV
22°
21°
0°
35°
100%
0%
100%
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
TEMPERATURE REGULATION
>
>
OK?
>
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
REGULATION TYPE 1
EXTR OK?
35°
15°
REGULATION TYPE
REGULATION
REGULATION TYPE 2
SUPPL OK?
COOLING
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
KJØLING
OK?
>
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
KJØLEGJENVINNING
NØYTRALSONE
AV
18°
MIN
180 s
OFF
1°
OK?
NEUTRAL ZONE
COOLNESS RECOVERY
HEAT RECOVERY SYSTEM
2°
1°
OK?
EXT. TEMP. CONTROL
EXT. TEMP. CONTROL
EXTERNAL TEMPERATURE CONTROL
OFF
OK?
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
FAN REGULATION
>
>
OK?
>
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
INLET AIR
OK?
50%
75%
100%
EXTRACT AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
EXTRACT AIR
OK?
50%
75%
100%
TIMER
STANDARD SPEED
STANDARD TIME
TIMER
OK?
MAX
30 m
AIR VOLUME COMPENSATION
SUPPLY AIR
EXTRACT AIR
AIR VOLUME COMPENSATION
OK?
MAX
MIN
CONFIGURATION
SENSORS
FIRE/SMOKE
COMMUNICATION
START/STOP SEQUENCE
REST MODE
CONFIGURATION
>
>
OK?
>
>
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
FILTER GUARD
SENSORS
>
>
OK?
>
>
SUPPLY AIR
CALIBRATION
INLET AIR
OK?
0
FILTER GUARD
ACTIVATION
PRESSURE GUARD
OK?
OFF
FIRE/SMOKE
MODE
FIRE/SMOKE
OK?
1
COMMUNICATION
HOME/AWAY
COMMUNICATION
OK?
HOME/AWAY
SPEED
TEMPERATURE
TIME DELAY
HOME/AWAY
OK?
MIN
18°
60 m
START/STOP SEQUENCE
START DELAY 1
START DELAY 2
START DELAY 3
START DELAY 4
STOP SEQUENCE EL
START/STOP SEQUENCE
OK?
0 s
20 s
20 s
20 s
180 s
REST MODE
SLEEP MODE
TIME DELAY
2 min OK?
OPERATING TIME
OPERATING TIME
OPERATING TIME
FILTER
312 tim
125 tim
TEST
FANS
HEATING
HEAT RECOVERY SYSTEM
COOLING
SENSORS
TEST
>
>
OK?
>
>
FANS
AC FANS
EC FANS
FANS
OK?
MIN
0%
HEATING
ACTIVATION
HEATING
OK?
OFF
HEAT RECOVERY SYSTEM
ACTIVATION
HEAT RECOVERY UNIT
OK?
OFF
COOLING
ACTIVATION
COOLING
OK?
OFF
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
TEMPERATURE SENSORS
22°
21°
0°
35°
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
OPERATING INFORMATION
MENU HANDLING 1
>
>
OK?
>
>
>
>
>
>
TIME AND DATE
13 : 45 04.07.09
MENU HANDLING 2
TIME DAY MONTH YEAR
OK?
TUESDAY
1
08
: 00 16 : 00
-
MIN
16°
2 16 : 00 18: 00
-
NORMAL
18°
3 18: 00 19 : 00
-
MAX
16°
4 19 : 00 24 : 00
-
NORMAL
18°
A new menu screen appears under each day.
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
MAIN MENU
LANGUAGE
NORSK
ENGLISH
SVENSKA
DEUTCH
NEDERLANDS
SUOMI
DANSK
OK?
TIME AND DATE
13 : 45 04.07.09
FILTER
INTERVAL CHANGE OF FILTER
RESET FILTER ALARM
INTERVAL CHANGE OF FILTER
6 MND
TIMER
SCREENSAVER
DAY / WEEK SETTINGS
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
OK?
TEMPERATURE
18
HEATING ELEMENT ON/OFF
HEATING ELEMENT ON
OK?
60 min
13.08.2009
16:43
18°C 22°C
- NORMAL
START MENU
LANGUAGE
TIME AND DATE
MAIN MENU
OK?
START UP MENU
SETTINGS
MAIN MENU 1
SETTINGS
MAIN MENU 2
MAIN MENU 2
>
>
>
OK?
MIN
NORMAL
MAX
MAX TIMER
MAIN MENU
SETTINGS
>
MAIN MENU
SETTINGS
>
MIN
NORMAL
MAX
MAX TIMER
OK?
MIN
NORMAL
MAX
MAX TIMER
OK?
>
>
OK?
>
>
>
>
>
TEMPERATURE 1
TEMPERATURE 2
OK?
HEATING ELEMENT ON/OFF
TIMER
TIME AND DATE
LANGUAGES
FILTER 2
FILTER 1
DAY/WEEK SETTINGS 1
DAY/WEEK SETTINGS 2
OK?
°C
TIME DAY MONTH YEAR
>
OK?
OK?
>
OK?
ALARM
RESET ALARM
ALARM
OK?
PIN CODE
PIN CODE
OK?
0 0 0 0
ADVANCED USER
TEMPERATURE REGULATION
FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
ADVANCED USER
>
OK?
>
>
>
>
OPERATING INFORMATION
SET TEMPERATURE
DAY / WEEK SETTINGS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
HEAT RECOVERY SYSTEM
COOLING
HEATING
OPERATING INFORMATION
22°
AKTIV
22°
21°
0°
35°
100%
0%
100%
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
TEMPERATURE REGULATION
>
>
OK?
>
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
REGULATION TYPE 1
EXTR OK?
35°
15°
REGULATION TYPE
REGULATION
REGULATION TYPE 2
SUPPL OK?
COOLING
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
KJØLING
OK?
>
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
KJØLEGJENVINNING
NØYTRALSONE
AV
18°
MIN
180 s
OFF
1°
OK?
NEUTRAL ZONE
COOLNESS RECOVERY
HEAT RECOVERY SYSTEM
2°
1°
OK?
EXT. TEMP. CONTROL
EXT. TEMP. CONTROL
EXTERNAL TEMPERATURE CONTROL
OFF
OK?
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
FAN REGULATION
>
>
OK?
>
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
INLET AIR
OK?
50%
75%
100%
EXTRACT AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
EXTRACT AIR
OK?
50%
75%
100%
TIMER
STANDARD SPEED
STANDARD TIME
TIMER
OK?
MAX
30 m
AIR VOLUME COMPENSATION
SUPPLY AIR
EXTRACT AIR
AIR VOLUME COMPENSATION
OK?
MAX
MIN
CONFIGURATION
SENSORS
FIRE/SMOKE
COMMUNICATION
START/STOP SEQUENCE
REST MODE
CONFIGURATION
>
>
OK?
>
>
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
FILTER GUARD
SENSORS
>
>
OK?
>
>
SUPPLY AIR
CALIBRATION
INLET AIR
OK?
0
FILTER GUARD
ACTIVATION
PRESSURE GUARD
OK?
OFF
FIRE/SMOKE
MODE
FIRE/SMOKE
OK?
1
COMMUNICATION
HOME/AWAY
COMMUNICATION
OK?
HOME/AWAY
SPEED
TEMPERATURE
TIME DELAY
HOME/AWAY
OK?
MIN
18°
60 m
START/STOP SEQUENCE
START DELAY 1
START DELAY 2
START DELAY 3
START DELAY 4
STOP SEQUENCE EL
START/STOP SEQUENCE
OK?
0 s
20 s
20 s
20 s
180 s
REST MODE
SLEEP MODE
TIME DELAY
2 min OK?
OPERATING TIME
OPERATING TIME
OPERATING TIME
FILTER
312 tim
125 tim
TEST
FANS
HEATING
HEAT RECOVERY SYSTEM
COOLING
SENSORS
TEST
>
>
OK?
>
>
FANS
AC FANS
EC FANS
FANS
OK?
MIN
0%
HEATING
ACTIVATION
HEATING
OK?
OFF
HEAT RECOVERY SYSTEM
ACTIVATION
HEAT RECOVERY UNIT
OK?
OFF
COOLING
ACTIVATION
COOLING
OK?
OFF
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
TEMPERATURE SENSORS
22°
21°
0°
35°
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
OPERATING INFORMATION
MENU HANDLING 1
>
>
OK?
>
>
>
>
>
>
TIME AND DATE
13 : 45 04.07.09
MENU HANDLING 2
TIME DAY MONTH YEAR
OK?
TUESDAY
1
08
: 00 16 : 00
-
MIN
16°
2 16 : 00 18: 00
-
NORMAL
18°
3 18: 00 19 : 00
-
MAX
16°
4 19 : 00 24 : 00
-
NORMAL
18°
Quick start guide CI600