FlameStop FDCIE Panels With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 32
4.2 Acknowledgement and Silence of Fault
A fault condition can be acknowledged and silenced from access level I.
Pressing the
SILENCE BUZZER
button under a fault condition, the buzzer of the FDCIE will be
silenced and the fault is acknowledged.
FAULT
LED will illuminate steadily.
4.3 Acknowledgement and Silence of Fire Alarm
A fire alarm can be acknowledged and silenced from access level II.
Pressing the
SILENCE BUZZER
button under fire alarm condition, the buzzer of the FDCIE will be
silenced and the fire alarm is acknowledged.
FIRE
LED and zone red LED will illuminate steadily.
4.4 Silencing the Sounder Outputs
The Sounder Outputs can be silenced at access level II.
Pressing the
SILENCE/RESOUND ALARM
button can silence the sounder outputs. In fire
condition, pressing the
SILENCE/RESOUND ALARM
button again will make them resound.
If the remote
SILENCE
input contact is shorted for over 2 seconds, the FDCIE will silence the
sounder outputs regardless of the current access level.
4.5 Evacuation
The evacuation can be operated at access level II.
Pressing the
EVAC
button, all sounder outputs will be started immediately. Pressing the
EVAC
button again, all sounder outputs will be stopped.
If the remote
EVAC
input contact is shorted for over 2 seconds, the FDCIE will activate EVAC
function to start all sounder outputs immediately regardless of the current access level.
4.6 Self-test and Reset
Self-test and reset can be carried out at access level II.
The FDCIE will start self-test on power-up. Pressing the
Reset
button can clear all audio and
visual indication and carry out self-test. The self-test can check all indicators and the buzzer. All
indicators illuminate and the buzzer sounds. After self-test, the panel returns to normal condition.
If the remote
RESET
input contact is shorted for over 2 seconds, the FDCIE will start reset and
self-test regardless of the current access level.