Functional description
Primary circuit:
The shunt group is controlled in the return line on the primary side using the NexusValve Vivax
control valve. The maximum capacity is set by presetting the valve. The flow in the primary circuit
can be variably adjusted by the actuator as required.
A primary pressure of 30 kPa is required at the valve for the system to function reliably.
Secondary circuit:
The flow rate must be greater in the secondary circuit than in the primary circuit. A suitable pump
must be selected for the secondary circuit in dependence on flow rate and pressure loss.
The flow rate in the secondary circuit can be set using the NexusValve Vertex if presetting using the
pump is not possible. When setting the flow rate using the pump, the valve must be fully open
(setting 9.9).
In the case of unregulated pumps, the flow rate can be set with the aid of the diagram for the NV
Vertex. The diagram illustrates the drop in pressure across the Vertex valve for a specified preset and
flow rate (see chap. 5.2).
Notes on dimensions:
Primary flow rate
≤
Secondary flow rate
ΔT primary ≥ ΔT secondary
ϑ
RL primary =
ϑ
RL secondary
Note:
The shunt groups are supplied without a heating circuit pump. This will need to be fitted and
connected by the customer.
Prim
ary
Se
co
nd
ar
y
Summary of Contents for MeiFlow Shunt UD DN15 S
Page 7: ...MeiFlow Shunt UD Last updated Aug 19 ENG Page 7 2 2 Dimensions...
Page 23: ...MeiFlow Shunt UD Senast uppdaterad aug 19 SWE Sida 23 2 2 M tt pump...
Page 39: ...MeiFlow Shunt UD Viimeksi p ivitetty elo 19 FIN Sivu 39 2 2 Mitat pumpp...
Page 55: ...MeiFlow Shunt UD Stand Mrz 21 Seite 55 2 2 Abmessungen DEU...