Integrated Control Equipment Curo
Supply air unit VEKA
3
Fläkt Woods
9965 GB 2016.09.27
Specifications are subject to alteration without notice
1. ElECtriCAl ConnECtionS
1.1 motorS
Size
power, kW
Current, A
Voltage, V
20
0,77 kW (0,385 kW x 2)
5 A (2,5 A x 2)
1 x 230 V
30
1,50 kW (0,75 kW x 2)
6,6 A (3,3 A x 2)
1 x 230 V
1.2 ElECtriCAl poSt hEAtEr
Size
power, kW
Current, A
Voltage, V
20
9
13
3 x 400 V
20
15
22
3 x 400 V
20
21
30
3 x 400 V
30
24
35
3 x 400 V
1.3 mAin Supply
NY BILD
!
The main supply cable must be fitted with an external safety
switch located close to the unit.
Ambient temperature 0 - 40 °C.
Main supply 1 x 230 V.
Fuse 10 A.
1
2
4
3
1. Control board
2. Transformer 230/24 V
3. Terminals