CO 

2

 control

Fläkt Woods STRZ-18-1-1 is an active CO 

2

 detector

(0-10V). This accessory provides the functionality that the

controller changes step by step from the normal nozzle

setting if required. The nozzle setting is increased when

the ppm level is in excess of the parameter 112 value

(500 ppm) and reaches the maximum nozzle setting

(parameter 305) when the ppm level is in excess of

paramater 113 (1000 ppm). Heating/cooling control (PI)

is preformed simultaneously with the CO 

2

 control and if

a cooling or heating need occurs the signal is directed to

respectively output (UO1 and UO2). Parameter 81 should

be set to 5 in order to activate the CO

2

 function.

Cooling

In control state Cooling, the unit is always a cooling

controller and controls according to the basic cooling

setpoint plus the setpoint displacement.

Cooling/Cooling

Split output signal

In control mode Cooling/Cooling, the controller always

functions as a cooling controller and controls according to

the basic cooling setpoint plus the setpoint displacement.

When the controller output signal reaches 50%, it is

divided between two actuators. 0…48% of the signal is

sent to actuator 1 and 52…100% of the signal is sent to

actuator 2. See the figure below.

Free cooling

In normal operation, the cooling sequence prioritize to

use water cooling, ie output UO2 where the water cooling

valve is connected. If not the water cooling is enough to

reach the set point, the airflow is increased step by step

by opening larger nozzles through UO3. Thus cooling

sequence is divided in 2 step, 0-50% is water cooling

and 51-100% is air cooling. Sometimes you got free

cooling by air, if outside temperature is cooler than the set

point room temperature. Then the STRA-14 can shift the

sequence so that 0-50% is air cooling and 51-100% is water

cooling. This is adjusted by changing the parameter 309.
309=0 Free cooling off – Water cooling 0-50% and 51-100%

air cooling

309=1 Free cooling on – Air cooling 0-50% and 51-100%

water cooling
Free cooling can also be turned on and off through

modbus communication.

Actuators

STRA-14 can be used with two types of actuators:
• Analogue 0…10 V actuators
• Thermal actuators
The actuator type is set via the parameter menu in the

display (parameter 20 and 21). Note that an adapter might

be needed if another actuator than Fläkt Woods STRZ-71

is used.

Analogue actuators

The following output signals can be set for analogue

actuators:
• 0…10 V (F5)
• 2…10 V
• 10…2 V
• 10…0 V

Thermal actuators

When thermal actuator control has been selected, this

is controlled digitally with time proportional pulses

via output UO…. By pulsing, the opening degree of the

actuator (and its valve) is varied. The period time (in

seconds) is the sum of the on and off. The period time is

FS=60s. The controller varies the on and off output times

proportionally depending on the output signal demand to

the actuator.

Actuator exercise

All actuators are exercised. The exercise takes place at

set intervals in hours (FS=23 hours interval). An opening

signal is sent to the actuator for as long time as the run

time has been configured. Then a closing signal is sent for

as long time and the exercise is finished.

Condensation detector

Special input CI

There is a special input (CI) on STRA-14 controllers.

This input is intended for Fläkt Woods’s condensation

detector, STRZ-16, and functions internally as a digital

input, I. e. condensation or no condensation.
When the condensation detector is activated, the cooling

control is blocked and the controller is set in neutral

position. When condensation ceases, the controller will

start controlling from the neutral position.

Window Contact

When the window contact has been configured, the

regulator is set to normal operation when window is

closed. If the window is open, the regulator is set in mode

off, heating and cooling outputs are set to 0 V and the

frost protection function is activated.

Summary of Contents for STRA-14

Page 1: ...or no parity Communication speed 9600 bps not changeable Built in temperature sensor NTC type measuring range 0 50 C accuracy 0 5 C at 15 30 C Material casing Polycarbonate PC Weight 110 g This produ...

Page 2: ...ecifications are subject of alteration without further notice Installation instructions Ensure that the installation complies with local safety regulations Information about commissioning of the produ...

Page 3: ...cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Display handling The display has the following indications Function button By pressing the Fu...

Page 4: ...lve actuator max 5 mA The valve actuator s 0 10 V control signal terminal is connected to terminal 23 and its supply terminals to terminals 10 and 11 Make sure that the reference pole G0 is connected...

Page 5: ...e is 22 C and the cooling setpoint value is 24 C the controller will allow the temperature in the room to be between 19 C and 27 C Local adjustment of setpoint value via the display on STRA 14 The bac...

Page 6: ...ed operating mode to attain energy efficiency Control states The controllers can be configured for different control states control sequences Parameter 11 FI 4 Heating Cooling with VAV control with fo...

Page 7: ...s air cooling and 51 100 is water cooling This is adjusted by changing the parameter 309 309 0 Free cooling off Water cooling 0 50 and 51 100 air cooling 309 1 Free cooling on Air cooling 0 50 and 51...

Page 8: ...prevents the temperature from dropping below 8 C Return to normal fan speed and control occurs automatically when the room temperature exceeds 8 C Control the light with an occupancy sensor It s possi...

Page 9: ...ng 1 2 3 4 5 6 STELLA 0 23 40 59 75 100 WEGA Standard 0 21 38 56 73 100 WEGA Power 0 23 23 23 23 100 NOVA 0 21 38 56 73 100 Nozzle selection for air flow in Energy Saving Mode and Boost Mode is adjust...

Page 10: ...10v 1 2 10v 2 10 2v 3 10 0v 0 29 Heating Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 30 Cooling Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 31 Heating Thermal Actu...

Page 11: ...or 1 For N O actuator 0 74 HMI Displacement View 0 The offset 1 The active setpoint offset 2 The heating setpoint offset 3 The cooling setpoint offset 4 Occupied Heating Setpoint Offset 5 Occupied Coo...

Page 12: ...28 Branch Version 129 Revision 300 Voltage x 10 for nozzle 2 21 301 Voltage x 10 for nozzle 3 38 302 Voltage x 10 for nozzle 4 56 303 Voltage x 10 for nozzle 5 73 304 Max air level at 100 cooling 5 30...

Reviews: