STRA-14 Room controller. Installation and maintenance manual.

Fläkt Woods

8710 GB 2016.09.08

11 (12)

Specifications are subject of alteration without further notice.

Parameter

number

Description

Values

Unit

FS STRA-14

49

Maximum airflow on cooling UO2 in % of 0-10V.

Parameter is in use when heating/cooling mode with

VAV is selected

%

0

50

Fan Control (Not in use)

0=No Control, 1=Heating,

2=Cooling, 3=Both

51

Fan Speed 1 Limit (Not in use)

%

52

Fan Speed 2 Limit (Not in use)

%

53

Fan Speed 3 Limit (Not in use)

%

54

Fan Start/Stop Hyst (Not in use)

55

Fan Speeds

56

External Temperature Sensor Calibration Gain AI1

°C

0

57

Sensor Calibration Gain UI1

°C

0

58

Internal Temperature Sensor Calibration Gain

°C

0

59

Filter factor for AI temperature

°C

0,2

60

Normally open/Normally closed DI1

0=N/O, 1=N/C

0

61

Normally open/Normally closed DI2

0=N/O, 1=N/C

1

62

Normally open/Normally closed UI1

0=N/O, 1=N/C

0

63

Heating Manual Override

0=Off, 1=Manual, 2=Auto

2

64

Cooling Manual Override

0=Off, 1=Manual, 2=Auto

2

65

Forced ventilation Manual Override

0=Off, 1=Manual, 2=Auto

2

66

Changeover Manual Override

0=Heating, 1=Cooling, 2=Auto

2

67

Manual Mode Heating Output

%

0

68

Manual Mode Cooling Output

%

0

69

Modbus Address

Set by production

(same as

EXOline ELA)

70

Modbus Parity

0=None, 1=Odd, 2=Even

2

71

Modbus Timeout

Milliseconds

3

72

Modbus Response Delay

Milliseconds

5

73

Heating output

0 = For N/C-actuator, 1=For N/O-

actuator

0

74

HMI Displacement View

0=The offset, 1=The active setpoint

+ offset, 2=The heating setpoint

+ offset, 3=The cooling se

offset, 4=Occupied Heating Setpoint

+ Offset, 5=Occupied Cooling

se Offset, 6=Occupied

A Offset

0

75

Free Cooling

0=Not Available, 1=Available

0

76

Forced Ventilation control mode

0=No Action, 1=Forced on Heat/

Cool output at 100%, 2=Forced on

Cool output at 100%

0

77

P.I.R Activated Operation Mode

3=Occupied, 4=Bypass

3

78

The Controller PLA Address. Used in EXOline

Set by Production

79

The Controller ELA Address. Used in EXOline

Set by Production

80

Cool output

0 = For N/C-actuator, 1=For N/O-

actuator

0

81

AI2 Input

0=Disable, 5=CO2, 7=0-100% ,

8=Flow calculation, 9=0-10V

0

82

Flow at 0 volt on AI2 (Not in use)

l/s

83

Flow at 10 volt at AI2 (Not in use)

l/s

84

The minimum time the valve is open when the

calculation of change over is made

Seconds

60

86

Alarm triggers when temperature falls below

°C

15

87

Alarm triggers when temperature raise above

°C

40

97

CO2 Level to Change to Boost Mode

PPM

1200

98

CO2 Level below "Boost Mode CO2 Start" value to

start Boost Mode Timer countdown

PPM

160

100

AI CO2 Filter

0,2

104

CO2 Sensor PPM for 0v

PPM

0

105

CO2 Sensor PPM for 10v

PPM

2000

112

VAV CO2 Minimum Limit

PPM

500

113

VAV CO2 Maximum Limit

PPM

1000

114

Port Mode

0=EXOline/Modbus, 1=BACnet

0

115

BACnet address

Above 127 = Slave

Set by Production

(Last 2 Digits of ELA)

116

BACnet device ID low 4 figures

Set by Production

("A" of PLA & ELA)

117

BACnet device ID high 3 figures

Set in Production,

uses "PL" of PLA

118

BACnet Max Master

127

Summary of Contents for STRA-14

Page 1: ...or no parity Communication speed 9600 bps not changeable Built in temperature sensor NTC type measuring range 0 50 C accuracy 0 5 C at 15 30 C Material casing Polycarbonate PC Weight 110 g This produ...

Page 2: ...ecifications are subject of alteration without further notice Installation instructions Ensure that the installation complies with local safety regulations Information about commissioning of the produ...

Page 3: ...cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Display handling The display has the following indications Function button By pressing the Fu...

Page 4: ...lve actuator max 5 mA The valve actuator s 0 10 V control signal terminal is connected to terminal 23 and its supply terminals to terminals 10 and 11 Make sure that the reference pole G0 is connected...

Page 5: ...e is 22 C and the cooling setpoint value is 24 C the controller will allow the temperature in the room to be between 19 C and 27 C Local adjustment of setpoint value via the display on STRA 14 The bac...

Page 6: ...ed operating mode to attain energy efficiency Control states The controllers can be configured for different control states control sequences Parameter 11 FI 4 Heating Cooling with VAV control with fo...

Page 7: ...s air cooling and 51 100 is water cooling This is adjusted by changing the parameter 309 309 0 Free cooling off Water cooling 0 50 and 51 100 air cooling 309 1 Free cooling on Air cooling 0 50 and 51...

Page 8: ...prevents the temperature from dropping below 8 C Return to normal fan speed and control occurs automatically when the room temperature exceeds 8 C Control the light with an occupancy sensor It s possi...

Page 9: ...ng 1 2 3 4 5 6 STELLA 0 23 40 59 75 100 WEGA Standard 0 21 38 56 73 100 WEGA Power 0 23 23 23 23 100 NOVA 0 21 38 56 73 100 Nozzle selection for air flow in Energy Saving Mode and Boost Mode is adjust...

Page 10: ...10v 1 2 10v 2 10 2v 3 10 0v 0 29 Heating Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 30 Cooling Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 31 Heating Thermal Actu...

Page 11: ...or 1 For N O actuator 0 74 HMI Displacement View 0 The offset 1 The active setpoint offset 2 The heating setpoint offset 3 The cooling setpoint offset 4 Occupied Heating Setpoint Offset 5 Occupied Coo...