STRA-14 Room controller. Installation and maintenance manual.

Fläkt Woods

8710 GB 2016.09.08

9 (12)

Specifications are subject of alteration without further notice.

Parameter Settings

STRA-14 is delivered with a number of factory settings. To acquire the desired function, the controller must be adapted

to it’s specific application. This is done through the parameter menu in the display. Applications may vary and

incorrectly set parameters can effect the controller and application negatively. Be sure to set the necessary parameters

relevant for your application. If you experience problems, contact Fläkt Woods TSS controls.

Parameter menu

It is possible to set different parameter values in a parameter menu. The parameter menu is accessed by simultaneously

holding the INCREASE and DECREASE buttons depressed for about 5 seconds and then pressing the INCREASE button

twice. The Service indication will be displayed.
First the display will show the parameter-number 1. Scroll between parameters by using the INCREASE and DECREASE

buttons.
Press the Function button to select the desired parameter. The parameter number will be replaced by the parameter

value. The value can be changed using the INCREASE and DECREASE buttons. If a button is held depressed the value

will start scrolling, first slowly and then with increasing speed in 3 – 4 steps with 2 – 3 seconds between steps.

WEGA Standard/WEGA Power, STELLA, NOVA

Parameter 307 is used to select nozzle for Normal air flow.

Hole setting 1

2

3

4

5

6

STELLA 0

23

40

59

75

100

WEGA Standard 0

21

38

56

73

100

WEGA Power 0

23

23

23

23

100

NOVA 0

21

38

56

73

100

Nozzle selection for air flow in Energy Saving Mode and Boost Mode is adjustable via parameter 306 and 308.
Energy Saving Mode is via Parameter 306, adjustable between nozzle selection 1-4.
Boost Mode is via Parameter 308, adjustable between nozzle selection 3-6.
The voltage x 10 for nozzle 2-5 has to be given in parameter 300-303. See table above for values for each nozzle for

different chilled beams (1 and 6 are fixed values.)

Acknowledge/Regret

To acknowledge and store a set parameter value, press the Function button again, the display then returns to showing

the parameter number. To retrieve the original value, i.e. the value before change, press the INCREASE and DECREASE

buttons at the same time. The original value is shown on the display.

Return

After a certain time, about 1 minute, or when the INCREASE and DECREASE buttons are pressed at the same time while

in the menu, the display returns to the normal view. Exit is shown on the display after the last parameter. The parameter

menu is exited by pressing the Function button while in Exit.

Parameter list

The following parameters can be changed in the parameter menu (FS = Factory setting):

Parameter

number

Description

Values

Unit

FS STRA-14

1

Occupied Heating Setpoint

°C

22

2

Occupied Cooling Setpoint

°C

24

3

Standby Neutral Zone

°C

3

4

Unoccupied Heating Setpoint

°C

19

5

Unoccupied Cooling Setpoint

°C

27

6

Frost protection Setpoint

°C

8

7

P-Band

°C

10

8

I-Time

Seconds

300

9

Cooling Changeover difference temperature (Room

and media)

°C

3

10

Heating Changeover difference temperature (Room

and media)

°C

4

Summary of Contents for STRA-14

Page 1: ...or no parity Communication speed 9600 bps not changeable Built in temperature sensor NTC type measuring range 0 50 C accuracy 0 5 C at 15 30 C Material casing Polycarbonate PC Weight 110 g This produ...

Page 2: ...ecifications are subject of alteration without further notice Installation instructions Ensure that the installation complies with local safety regulations Information about commissioning of the produ...

Page 3: ...cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Display handling The display has the following indications Function button By pressing the Fu...

Page 4: ...lve actuator max 5 mA The valve actuator s 0 10 V control signal terminal is connected to terminal 23 and its supply terminals to terminals 10 and 11 Make sure that the reference pole G0 is connected...

Page 5: ...e is 22 C and the cooling setpoint value is 24 C the controller will allow the temperature in the room to be between 19 C and 27 C Local adjustment of setpoint value via the display on STRA 14 The bac...

Page 6: ...ed operating mode to attain energy efficiency Control states The controllers can be configured for different control states control sequences Parameter 11 FI 4 Heating Cooling with VAV control with fo...

Page 7: ...s air cooling and 51 100 is water cooling This is adjusted by changing the parameter 309 309 0 Free cooling off Water cooling 0 50 and 51 100 air cooling 309 1 Free cooling on Air cooling 0 50 and 51...

Page 8: ...prevents the temperature from dropping below 8 C Return to normal fan speed and control occurs automatically when the room temperature exceeds 8 C Control the light with an occupancy sensor It s possi...

Page 9: ...ng 1 2 3 4 5 6 STELLA 0 23 40 59 75 100 WEGA Standard 0 21 38 56 73 100 WEGA Power 0 23 23 23 23 100 NOVA 0 21 38 56 73 100 Nozzle selection for air flow in Energy Saving Mode and Boost Mode is adjust...

Page 10: ...10v 1 2 10v 2 10 2v 3 10 0v 0 29 Heating Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 30 Cooling Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 31 Heating Thermal Actu...

Page 11: ...or 1 For N O actuator 0 74 HMI Displacement View 0 The offset 1 The active setpoint offset 2 The heating setpoint offset 3 The cooling setpoint offset 4 Occupied Heating Setpoint Offset 5 Occupied Coo...

Page 12: ...28 Branch Version 129 Revision 300 Voltage x 10 for nozzle 2 21 301 Voltage x 10 for nozzle 3 38 302 Voltage x 10 for nozzle 4 56 303 Voltage x 10 for nozzle 5 73 304 Max air level at 100 cooling 5 30...

Reviews: