background image

Fläkt Woods 

8061 GB  2009.05 

17 

Specifications are subject to alteration without further notice.

RoomMaster ABR-2 

COMMISSIONING

Alarm and fault-finding

The alarm message is displayed in the window in clear text at the same time as a red LED flashes on the control panel.

  Alarm message 

Operation 

Cause 

Remedy 

 

Unit stops 

Power supply to motor interrupted. 

Contact a service engineer. Check   

 

 

the motor connections, any integral  

overheating protection and the 

 

 

 

motor. 

 

 

 

 

 

Unit stops 

Power supply to motor interrupted. 

Contact a service engineer. Check   

 

 

themotor connections, any integral  

overheating protection and the

 

 

 

rotor.

 

Unit stops 

Sensor signal to control card  

Contact a service engineer to check  

 

 

interrupted or unacceptable. 

the sensors.

 
 

Unit in operation 

Sensor signal to control card 

Contact a service engineer to check

 

Room regulation  

interrupted or unacceptable. 

the sensors.

 

switched automatically

 

to supply air regulation

 

Unit stops 

Supply air temperature has fallen 

Check the exhaust air temperature

 

  

below the set desired value by 10 

(see window 21).

 

 

degrees for more than 15 minutes. 

Check the setting of the lowest  

 

 

This may occur if there is a fault in:  

supply air temperature

 

 

heat exchanger, electric coil. 

15c).  

 (see windows 15b or  

 

 

 

 

It may also be due to low room 

Check the heat exchanger and electric

 

 

temperature and setting of operating 

coil (see Alarm, heat exchanger and

 

 

data, such as: stopping the unit  

electric coil).

 

 

without a damper, lowest supply air 

Check that an electric coil is installed

 

 

temp. too high, electric heater not 

(see window 75).

 

 

connected. 

Check setting of operating mode (see  

 

 

If a presence sensor is fitted, the 

windows 30 and 40).

 

 

unit will stop if the "no effect" 

Check whether a damper is fitted in

 

 

activity is selected for period 1 

the outdoor air duct, and setting of

 

 

(see window 41a) 

activity.

 

Unit in operation 

No output or low efficiency from 

Check that the heat exchanger drive  

 

 

heat exchanger. 

belt is sound and fully tensioned.

 

Unit in operation 

Power supply interrupted. 

Check the electric coil connections

 

 

Overheating protection tripped. 

and overheating protection.

 

 

 

Reset the overheating protection

 

 

 

on the electric coil.

 
 

Unit in operation 

Block filters. 

Replace the filter and re-calibrate.

 

 

An alarm with clean filters indicates

 

 

that calibration was NOT carried out

 

 

during installation.

Acknowledgement of alarm text is done by pressing 

once; the alarm text disappears, and the LED continues to flash.

Press  

once more to activate selftest.

AUTO

AUTO

ALARM

Fan, supply air

ALARM

Fan, exhaust air

ALARM

Temp.sensor supp air

ALARM

Temp.sensor exh. air

ALARM

Low supply air temp.

ALARM

HE- rotor not work.

ALARM

Elec.Coil not working

ALARM

Replace air filter

Procedure - setting

Summary of Contents for RoomMaster ABR-2

Page 1: ...RoomMaster ABR 2 Commissioning...

Page 2: ...PROCEDURE SETTING Setting of temperature regulation of desired value for temperature 7 Setting of exhaust air flow standard and reduced flow and supply air exhaust air flow ratio 8 Reading actual valu...

Page 3: ...ed at any time for a new operating status by pressing the appropriate operating mode key Five setting keys are provided to set and read the air flows and temperatures etc to increase and reduce the va...

Page 4: ...ng Fig 21 10 50 20 40 80 60 30 70 11 14 12 17 13 15 12d Huvudmeny Undermeny 1 Undermeny 2 12e 12b 12a 12c 16 Function of setting keys Sub menu 2 Sub menu 1 Main menu Fig 22 Main menu and sub menu Next...

Page 5: ...which interrupts calibration before it is com plete the calibration procedure must be repeated Unit self test Self test is intended to be used for checking important components in the unit during serv...

Page 6: ...ing has been left lying inside the unit 3 Push the plug into an earthed wall socket 4 Activate the setting keys 3 5 Choice of language in text window 14 81 6 Perform setting of Standard flow and Reduc...

Page 7: ...s the key Window 15 is displayed 6 Press the key Window 15a is displayed 10 0 30 0 C 20 0 C 7 Change to the desired value with and confirm with cursor stops flashing 8 Press the key Window 15b is disp...

Page 8: ...is displayed 2 Press the key Window 20 is displayed 3 Press the key Window 21 is displayed current exhaust air temperature can be read 4 Press the key Window 22 is displayed current supply air temper...

Page 9: ...Window 31d is displayed Standard flow Reduced flow Stop 11 Change to desired activity 2 with and confirm with cursor stops flashing 12 Press the key Window 31 is displayed 13 Press the key Window 32...

Page 10: ...firm with cursor stops flashing 10 Press the key Window 41 is displayed 11 Press the key Window 42 is displayed 12 Repeat the above procedure to set the desired operating times and operating modes for...

Page 11: ...irm with cursor stops flashing 5 Press the key Window 52 is displayed Month Day 6 Set the date with and confirm with cursor stops flashing 7 Press the key Window 53 is displayed Weekday 8 Set the week...

Page 12: ...temperature with and confirm with cursor stops flashing 7 Press the key Window 63 is displayed 16 0 32 0 C 22 0 C 8 Change to the desired temperature with and confirm with cursor stops flashing 9 Pre...

Page 13: ...prox 5 minutes Self test of unit Window 71a 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3 Press the key Window 71...

Page 14: ...00 34b Activity 1 Thursday Standard flow 34c Change over time 2 Thursday 17 00 34d Activity 2 Thursday Reduced flow Window Description Default value No 35a Change over time 1 Friday 8 00 Weekly rhythm...

Page 15: ...the operating window Activation of electric coil and cooling coil 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3...

Page 16: ...key to confirm Press the key twice to return to the operating window Function The unit operates at reduced flow when the presence sensor does NOT sense any movement in the room N B For normal air hand...

Page 17: ...be due to low room Check the heat exchanger and electric temperature and setting of operating coil see Alarm heat exchanger and data such as stopping the unit electric coil without a damper lowest su...

Page 18: ...Outdoor temperature not below 12 0 C 43 Set time activity period 3 53 Set weekday Monday 54 Set time 14 34 h m 71a Self test 71 Test Calibration Default value 71c Reset to default values 71b Calibrati...

Page 19: ...No 76 Cooling coil installed No 77 Program version 1 0 Language 80 Main menu Select language 81 Language English Procedure setting Wind Description Default Own No value setting Air flow 10 Main menu...

Page 20: ...Fl kt Woods AB 551 84 J nk ping t 036 19 30 00 f 036 19 36 20 w www flaktwoods com FWG_AHU_ABR2 Technical instruction_2009 05_GB_8061 Condesign Info Productions AB ABF5533...

Reviews: