FlaktWoods RoomMaster ABR-2 Commissioning Download Page 5

Fläkt Woods 

8061 GB  2009.05 

Specifications are subject to alteration without further notice.

RoomMaster ABR-2 

COMMISSIONING

Example: Changing standard flow

The standard flow must be changed from 200 l/s to 220 

l/s. Activation of the setting keys brings you automati-

cally into the main menu with window number 10.

Press key   

to show window 11

Press key   

until 220 l/s is displayed

Press key  

to confirm

Factory settings on delivery

Self-test and Calibration are always carried out prior to 

delivery from the factory. Setting and checking the func-

tion are adapted to suit the ordered variant and the speci-

fied accessories.
The following functions/accessories influence the setting:

 

Electric coil installed

 

Cooling installed

 

Presence sensor as an accessory

Calibration of unit

The unit must always be calibrated for a new installation. 

The calibration time is approx. 5 minutes.

During calibration the control unit checks the prevail-

ing operating condition and adapts the operating point of 

thefans to the selected setting data.

Interrupted calibration

In the event of a power supply failure or other operating 

 breakdown which interrupts calibration before it is com-

plete the calibration procedure must be repeated.

Unit self-test

Self-test is intended to be used for checking important 

components in the unit during service and after correct-

ing any faults.

The self-test time is approx. 20 minutes.

Alarm

In the event of an alarm, the response should be as in-

dicated in the alarm message (see also PROCEDURE - 

Alarm and fault-finding).

Activate self-test by pressing “AUTO“ twice.

The unit switches automatically to automatic mode once 

self-test is complete. The self-test time depends on the 

type of fault.

Selecting operating mode STOP

It is recommended that the unit is operated continuously 

for normal air treatment. In order to be able to select the 

STOP operating mode, dampers are required in the out-

door air and the extract air duct. The absence of a damper 

will allow impurities to enter the unit by “the back way“, 

and the room and the unit will be cooled down during 

cold times of the year. Cooling of the room leads to in-

creased heating costs and increases the risk of operating 

breakdowns with the unit.

10 Ställ in 
    börvärde 

50

20

40

80

60

30

70

15

12

11 Normalflöde:
     200 l/s          

13

14

16

Huvudmeny

Undermeny 1

Fig. 23. Example: Changing standard flow.

Sub-menu 1

Main menu

11 Standard 

flow: 200 l/s

10 Set desi-

    red value

Commissioning - start-up

Summary of Contents for RoomMaster ABR-2

Page 1: ...RoomMaster ABR 2 Commissioning...

Page 2: ...PROCEDURE SETTING Setting of temperature regulation of desired value for temperature 7 Setting of exhaust air flow standard and reduced flow and supply air exhaust air flow ratio 8 Reading actual valu...

Page 3: ...ed at any time for a new operating status by pressing the appropriate operating mode key Five setting keys are provided to set and read the air flows and temperatures etc to increase and reduce the va...

Page 4: ...ng Fig 21 10 50 20 40 80 60 30 70 11 14 12 17 13 15 12d Huvudmeny Undermeny 1 Undermeny 2 12e 12b 12a 12c 16 Function of setting keys Sub menu 2 Sub menu 1 Main menu Fig 22 Main menu and sub menu Next...

Page 5: ...which interrupts calibration before it is com plete the calibration procedure must be repeated Unit self test Self test is intended to be used for checking important components in the unit during serv...

Page 6: ...ing has been left lying inside the unit 3 Push the plug into an earthed wall socket 4 Activate the setting keys 3 5 Choice of language in text window 14 81 6 Perform setting of Standard flow and Reduc...

Page 7: ...s the key Window 15 is displayed 6 Press the key Window 15a is displayed 10 0 30 0 C 20 0 C 7 Change to the desired value with and confirm with cursor stops flashing 8 Press the key Window 15b is disp...

Page 8: ...is displayed 2 Press the key Window 20 is displayed 3 Press the key Window 21 is displayed current exhaust air temperature can be read 4 Press the key Window 22 is displayed current supply air temper...

Page 9: ...Window 31d is displayed Standard flow Reduced flow Stop 11 Change to desired activity 2 with and confirm with cursor stops flashing 12 Press the key Window 31 is displayed 13 Press the key Window 32...

Page 10: ...firm with cursor stops flashing 10 Press the key Window 41 is displayed 11 Press the key Window 42 is displayed 12 Repeat the above procedure to set the desired operating times and operating modes for...

Page 11: ...irm with cursor stops flashing 5 Press the key Window 52 is displayed Month Day 6 Set the date with and confirm with cursor stops flashing 7 Press the key Window 53 is displayed Weekday 8 Set the week...

Page 12: ...temperature with and confirm with cursor stops flashing 7 Press the key Window 63 is displayed 16 0 32 0 C 22 0 C 8 Change to the desired temperature with and confirm with cursor stops flashing 9 Pre...

Page 13: ...prox 5 minutes Self test of unit Window 71a 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3 Press the key Window 71...

Page 14: ...00 34b Activity 1 Thursday Standard flow 34c Change over time 2 Thursday 17 00 34d Activity 2 Thursday Reduced flow Window Description Default value No 35a Change over time 1 Friday 8 00 Weekly rhythm...

Page 15: ...the operating window Activation of electric coil and cooling coil 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3...

Page 16: ...key to confirm Press the key twice to return to the operating window Function The unit operates at reduced flow when the presence sensor does NOT sense any movement in the room N B For normal air hand...

Page 17: ...be due to low room Check the heat exchanger and electric temperature and setting of operating coil see Alarm heat exchanger and data such as stopping the unit electric coil without a damper lowest su...

Page 18: ...Outdoor temperature not below 12 0 C 43 Set time activity period 3 53 Set weekday Monday 54 Set time 14 34 h m 71a Self test 71 Test Calibration Default value 71c Reset to default values 71b Calibrati...

Page 19: ...No 76 Cooling coil installed No 77 Program version 1 0 Language 80 Main menu Select language 81 Language English Procedure setting Wind Description Default Own No value setting Air flow 10 Main menu...

Page 20: ...Fl kt Woods AB 551 84 J nk ping t 036 19 30 00 f 036 19 36 20 w www flaktwoods com FWG_AHU_ABR2 Technical instruction_2009 05_GB_8061 Condesign Info Productions AB ABF5533...

Reviews: