COMMISSIONING

Activation (blocking) of operating mode keys

1. Press the 

 

keys at the same time for approx. 5 seconds. Window 10 is displayed 

2. Press the 

key (6 times) until window 70 is displayed 

3. Press the 

key. Window 71 is displayed 

4. Press the 

key. Window 72 is displayed 

No - Yes

5. Select Yes or No with 

, and confirm with 

(cursor stops flashing)

6. Press the 

key, once. Window 73 is displayed 

No - Yes

7. Select Yes or No with 

, and confirm with 

(cursor stops flashing)

8. Press the 

key, once. Window 74 is displayed  

No - Yes

9. Select Yes or No with 

 

, and confirm with 

(cursor stops flashing)

10. Press the 

key twice to return to the operating window.

Activation of electric coil and cooling coil

1. Press the 

keys at the same time for approx. 5 seconds. Window 10 is displayed 

2. Press the 

key (6 times) until window 70 is displayed 

3. Press the 

key. Window 71 is displayed  

  No - Yes

4. Press the 

key (4 times) until window 75 is displayed  

  No - Yes

5. Select Yes or No with 

, and confirm with  

 (cursor stops flashing)

6. Press the 

key. Window 76 is displayed 

No - Recycling - Cooling coil/recycling

7. Select Yes or No with 

, and confirm with 

(cursor stops flashing)

8. Press the 

key twice to return to the operating window.

STOP

10
Set desired value

70 Test /Default value
/ Configuration

71 Test /Calibration
/ Default value

72   Overtime button
activated        Yes

73 Ventilation button
activated      Yes

74      Stop button 
activated           Yes

10
Set desired value

70 Test /Default value
/ Configuration

71 Test /Calibration
/ Default value

75    Electrical coil
installed       Yes

76   Cooling

       No

Procedure - setting

Summary of Contents for RoomMaster ABR-2

Page 1: ...RoomMaster ABR 2 Commissioning...

Page 2: ...PROCEDURE SETTING Setting of temperature regulation of desired value for temperature 7 Setting of exhaust air flow standard and reduced flow and supply air exhaust air flow ratio 8 Reading actual valu...

Page 3: ...ed at any time for a new operating status by pressing the appropriate operating mode key Five setting keys are provided to set and read the air flows and temperatures etc to increase and reduce the va...

Page 4: ...ng Fig 21 10 50 20 40 80 60 30 70 11 14 12 17 13 15 12d Huvudmeny Undermeny 1 Undermeny 2 12e 12b 12a 12c 16 Function of setting keys Sub menu 2 Sub menu 1 Main menu Fig 22 Main menu and sub menu Next...

Page 5: ...which interrupts calibration before it is com plete the calibration procedure must be repeated Unit self test Self test is intended to be used for checking important components in the unit during serv...

Page 6: ...ing has been left lying inside the unit 3 Push the plug into an earthed wall socket 4 Activate the setting keys 3 5 Choice of language in text window 14 81 6 Perform setting of Standard flow and Reduc...

Page 7: ...s the key Window 15 is displayed 6 Press the key Window 15a is displayed 10 0 30 0 C 20 0 C 7 Change to the desired value with and confirm with cursor stops flashing 8 Press the key Window 15b is disp...

Page 8: ...is displayed 2 Press the key Window 20 is displayed 3 Press the key Window 21 is displayed current exhaust air temperature can be read 4 Press the key Window 22 is displayed current supply air temper...

Page 9: ...Window 31d is displayed Standard flow Reduced flow Stop 11 Change to desired activity 2 with and confirm with cursor stops flashing 12 Press the key Window 31 is displayed 13 Press the key Window 32...

Page 10: ...firm with cursor stops flashing 10 Press the key Window 41 is displayed 11 Press the key Window 42 is displayed 12 Repeat the above procedure to set the desired operating times and operating modes for...

Page 11: ...irm with cursor stops flashing 5 Press the key Window 52 is displayed Month Day 6 Set the date with and confirm with cursor stops flashing 7 Press the key Window 53 is displayed Weekday 8 Set the week...

Page 12: ...temperature with and confirm with cursor stops flashing 7 Press the key Window 63 is displayed 16 0 32 0 C 22 0 C 8 Change to the desired temperature with and confirm with cursor stops flashing 9 Pre...

Page 13: ...prox 5 minutes Self test of unit Window 71a 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3 Press the key Window 71...

Page 14: ...00 34b Activity 1 Thursday Standard flow 34c Change over time 2 Thursday 17 00 34d Activity 2 Thursday Reduced flow Window Description Default value No 35a Change over time 1 Friday 8 00 Weekly rhythm...

Page 15: ...the operating window Activation of electric coil and cooling coil 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3...

Page 16: ...key to confirm Press the key twice to return to the operating window Function The unit operates at reduced flow when the presence sensor does NOT sense any movement in the room N B For normal air hand...

Page 17: ...be due to low room Check the heat exchanger and electric temperature and setting of operating coil see Alarm heat exchanger and data such as stopping the unit electric coil without a damper lowest su...

Page 18: ...Outdoor temperature not below 12 0 C 43 Set time activity period 3 53 Set weekday Monday 54 Set time 14 34 h m 71a Self test 71 Test Calibration Default value 71c Reset to default values 71b Calibrati...

Page 19: ...No 76 Cooling coil installed No 77 Program version 1 0 Language 80 Main menu Select language 81 Language English Procedure setting Wind Description Default Own No value setting Air flow 10 Main menu...

Page 20: ...Fl kt Woods AB 551 84 J nk ping t 036 19 30 00 f 036 19 36 20 w www flaktwoods com FWG_AHU_ABR2 Technical instruction_2009 05_GB_8061 Condesign Info Productions AB ABF5533...

Reviews: