Fläkt Woods
8666 GB 2010.06
Specifications are subject to alteration without notice
Installation and maintenance instructions
Control equipment
5
Control panel, size 7.5 and 11–15 kW
1. Connecting the lighting switch
2. Display connector, (HMI*), Ethernet, USB
3. Circuit board with terminal blocks for accessories
4. Space for a communication module
5. SD card reader
6. Modem
7. Earthing bar
8. Transformer
9. Junction box connections
10. Glass fuses, power supply 24 VAC and 24 VDC
11. A and B alarm outputs
12. Start/Operation Heating/Cooling
13. Incoming supply for service lighting
14. Incoming supply, 7.5 kW–15 kW
a. Connecting phases
b. Connecting neutral
15. Control panel electrical supply
16. Power supply, air handling unit loads, 3-phase.
17. Internal maneuvre (read switch)
18. Air handling unit load short-circuit protection
* It is also possible to connect the display via KNX
(for example for outdoor units where longer cable is
needed).
Please note that the response time decreases when
using this connection.
Electrical connections and currents,
power units 7.5 kW and 11–15 kW
Connect the incoming supply to earth (7) - and neutral
terminal block 14 b and phases L1, L2 and L3 to terminal
block group 14 a (see the figure above) in the control
panel. If the STAZ-81 energy analyser has been selected,
connect the incoming supply directly to the energy ana-
lyser (see page 10). Connect the protective earth directly
to the earthing bar, 7, (see the figure above).
Each incoming supply must be provided with a manu-
ally operated lockable main circuit breaker/load inter-
rupter confirming to Machinery Directive 2006/42/EC
and Standard EN 60204-1 Electrical equipment of machi
-
nes. The load interrupter is available as an accessory
(STAZ-80). The safety circuit breaker is available as a
motor accessory (APAC). Protect the incoming power
supply of the air handling unit with a fuse in accordance
with current legislation in the country where the equip-
ment is installed.
Fig. 2 Control panel, size 7.5 and 11–15 kW
HMI
TCP/IP
USB
B
U
S
BSP
RESET
MODE
M
MEMORY CARD
1
2
17
3
4
5
7
8
9
10
11
12
13
14 a
14 b
15
18
16
2
24 VAC
24 VDC
6