Function
Terminal block
Connection
Comment
Supply air sensor
GT1
Quick-fit connector Type PT1000
Outdoor temp. sensor
GT3
Quick-fit connector Type PT1000
Z input
GT4
Quick-fit connector Type PT1000
Frost protection sensor
GT5
Quick-fit connector Type PT1000
Extract air sensor
GT12
Quick-fit connector Type PT1000
Filter monitor (supply/extract air GP1-2
Quick-fit connector NO
Fan monitor (supply/extract air)
GP3-4
Quick-fit connector NC
Pressure monitor -
heat exchanger defrost
GP7
Quick-fit connector NO
Heating
Heating
Quick-fit connector Heating control signal
Cooling
Cooling
Quick-fit connector Cooling control signal
Recovery
Recovery
Quick-fit connector Heat exchanger control signal
Mixing damper
Mixing
Quick-fit connector Mixing damper control signal
Damper actuators
ST1 – 2
Quick-fit connector Control signal, damper actuator,
24 VAC
Pressure/flow sensor
GP5-6/GF1-2
Quick-fit connector Measurement signal and
power supply
Flow sensor/fan alarm
GF1-2/L.TF/FF Quick-fit connector Measurement signal and
power supply
BUS-communication
Modbus
Quick-fit connector Connection BUS communication.
Type of minutes selected on the
control panel.
Fan control
TF1/FF1
Quick-fit connector Control signal supply and
extract air fan
Alarm
Alarm
Quick-fit connector Connecting alarm CP1, CP2 and
alarm SAF/EAF.