10
Fläkt Woods
8666 GB 2010.06
Specifications are subject to alteration without notice
Installation and maintenance instructions
Control equipment
Connecting the energy analyser
Cable dimensions and currents, 0.55 – 15 kW
Outputs, power unit,
kW (3x400 VAC)
Maximum cross section of the
internal motor cable, mm
2
(A)
Maximum cross section of the
external electrical power supply,
mm
2
(A)
0,55-5,5
2,5
4 (max. 25 A)
7,5
2,5
16 (max. 63 A)
11-15
6
25 (max. 80 A)
Fuse protection for DX-cooling, electrical heating and ECONET is carried out separately.
Incoming phase
Energy analyser
incoming
terminal block
Energy analyser
outgoing
terminal block
L1 (U)
3
1
L2 (V)
6
4
L3 (W)
9
7
43
42
41
9
6
3
Fig. 8
Energy meters: Connecting L1 (U), L2 (V) and L3 (W).
Connect neutral (N) and earth (PE) to the specified terminal block.
7
4
1
11