15
OWNER’S MANUAL
NEUTON™
Screen
Display Conditions
Home
The sensor has had no user
interaction for 5 seconds .
Setpoint
adjustment
Press the
or
buttons .
Information Press the button . Tap the
button to cycle through various
information .
Diagnostic Hold the button for 3
seconds . Tap the button
to cycle through various
information to troubleshoot your
system .
Zone Sensor Metrics
Temperature and Humidity (standard), CO
2
(optional)
Occupied indicator
Sensing Element Range Accuracy: Temperature 50° F to 104° F (10° C to 40° C)
±
0 .5° F (0 .3° C) Humidity 10% to 90%
±
1 .8% typical CO2
±
30PPM or +/
±
3% of reading
Power Requirements/Supply: DDC controller supplies the Rnet zone sensor with 12 Vdc @ 210 mA . (no additional
power required)
Communication: 115 kbps Rnet connection between sensor(s) and controller
Local Access Port: For connecting a laptop computer to the local equipment for maintenance and commissioning
Mounting Dimensions: Standard 4”x 2” electrical box using provided 6/32” x 1/2” mounting screws
The ZS Pro sensor is designed for integration with the I/O Zone 583 DDC controller .
Communications are established using the Rnet communications port and only a 4 wire connection is required even if
the combined temperature, relative humidity and CO sensor is utilized .
If the NEUTON is connected to a network via BACnet and/or the zone conditions are provided to the pump module in
this manner, an additional connection is easily made at the BACnet communications port standard at the 583 DDC
controller . See electrical diagram provided .