EasyGrid LT User Guide
24
5
Wiring information
General
5.1
-
The following section is a recommendation, you must conform with your local electrical code.
-
Use copper wire, solid or stranded. Copper wire ferrules can be used with stranded conductors.
Terminal
block
Part number
Manufacturer
Recommended
screwdriver blade
Recommended
torque
Recommended
strip length
Wire size range
Power
1827635
Phoenix Contact
0.4 x 2.5mm
0.23Nm
7mm
0.33 – 1.5mm
2
Analog
output
1803594
Phoenix Contact
0.4 x 2.5mm
0.23Nm
7mm
0.2 – 1.5mm
2
System relay
1803581
Phoenix Contact
0.4 x 2.5mm
0.23Nm
7mm
0.2 – 1.5mm
2
RS-422/485
1803604
Phoenix Contact
0.4 x 2.5mm
0.23Nm
7mm
0.2 – 1.5mm
2
Relays
1946570000
Weidmuller
0.6 x 3.5mm
0.45Nm
7mm
0.2 – 2.5mm
2