3.IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a
digital tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
V
W
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
U
N
V
W
4.Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
RPG20E
RPG45C
Black - Red
430Ω±8% (20
℃
)
(Brand: Dayang)
388Ω±8% (20
℃
)
(Brand: Weiling)
175Ω±8% (20
℃
)
(Brand: Dayang)
168Ω±8% (20
℃
)
(Brand: Weiling)
White - Black
370Ω±8% (20
℃
)
(Brand: Dayang)
360Ω±8% (20
℃
)
(Brand: Weiling)
105Ω±8% (20
℃
)
(Brand: Dayang)
141Ω±8% (20
℃
)
(Brand: Weiling)
Summary of Contents for FSAIF-Pro-123AE2
Page 8: ...8 O optional function ...
Page 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Page 14: ...14 FSAIF Pro 123AE2 ...
Page 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Page 16: ...16 FSOAIF Pro 123AE2 ...
Page 17: ...17 FSOAIF Pro 183AE2 ...
Page 18: ...18 FSOAIF Pro 243AE2 ...
Page 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...