For other motors:
NO.
1
2
3
4
5
Color
Orange
Grey
White
Pink
Black
Signal
Hu
Hv
Hw
Vcc
GND
Color
Red
Blue
Yellow
Signal
W
V
U
1) Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not
equal to each other, the fan motor must has problems and need to be replaced. Otherwise, go to
step 2.
2) Power on and when the unit is in standby, measure the voltage of pin4-5 in feedback signal
connector. If the value is not 5V, change the PCB. Otherwise, go to step 3.
Index2:
1: Indoor AC Fan Motor
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds,
measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power
supply)or 50V(115V power supply), the PCB must has problems and need to be replaced.
2. Indoor or Outdoor DC Fan Motor(control chip is in fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must has
problems and need to be replaced.
Summary of Contents for FSAIF-Pro-123AE2
Page 8: ...8 O optional function ...
Page 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Page 14: ...14 FSAIF Pro 123AE2 ...
Page 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Page 16: ...16 FSOAIF Pro 123AE2 ...
Page 17: ...17 FSOAIF Pro 183AE2 ...
Page 18: ...18 FSOAIF Pro 243AE2 ...
Page 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...