![Fisher FSAIF-Pro-123AE2 Service Manual Download Page 19](http://html.mh-extra.com/html/fisher/fsaif-pro-123ae2/fsaif-pro-123ae2_service-manual_2294428019.webp)
19
6 Installation Details
6.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
Ф15.9
5/8
4500(459kgf.cm)
4700(479kgf.cm)
Ф19
3/4
6500(663kgf.cm)
6700(683kgf.cm)
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Capacity kBTU/h
Nominal cross-sectional area (mm²)
9
3x2,5
12
3x2,5
18
3x2,5
24
3x2,5
The cable size and the current of the fuse or switch are determined by the maximum current indicated
on the nameplate which located on the side panel of the unit. Please refer to the nameplate before
selecting the cable, fuse and switch.
Summary of Contents for FSAIF-Pro-123AE2
Page 8: ...8 O optional function ...
Page 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Page 14: ...14 FSAIF Pro 123AE2 ...
Page 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Page 16: ...16 FSOAIF Pro 123AE2 ...
Page 17: ...17 FSOAIF Pro 183AE2 ...
Page 18: ...18 FSOAIF Pro 243AE2 ...
Page 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...