9.
Electronic control function
8.1 Abbreviation
T1: Indoor ambient temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet(This sensor is located in outdoor unit)
T3: Coil temperature of outdoor heat exchanger
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Setting temperature
8.2 Electric control working environment.
8.2.1 Input voltage: 198V~264V.
8.2.2 Input power frequency:50Hz.
8.2.3 Indoor fan normal working amp. is less than 1A.
8.2.4 Outdoor fan. normal working amp. is less than 1.5A.
8.2.5 Four-way valve normal working amp. is less than 1A.
8.3 Outdoor unit’s digital display tube
There is a digital display tube in outdoor PCB.
Digital display tube display function
In standby , the LED displays “- -”
In compressor operation, the LED display the running frequency,
In defrosting mode, The LED displays “dF” or alternative displays between running frequency and
“dF”(each displays 0.5s)
In compressor pre-heating, The LED displays “PH” or alternative displays between running frequency
and “PH”(each displays 0.5s)
During the oil return process, The LED displays “RO” or alternative displays between running
frequency and “RO”(each displays 0.5s)
In low ambient cooling mode, the LED displays “LC” or alternative displays between running
frequency and “LC”(each displays 0.5s)
In forced cooling mode, the LED displays “FC” or alternative displays between running frequency and
“FC”(each displays 0.5s)
When PFC module protection occurs three times within 15 minutes, the LED displays “E6” or
alternative displays between running frequency and “E6”(each displays 0.5s)
In protection or malfunction, the LED displays error code or protection code.
Summary of Contents for FS2MIF-141AE2
Page 8: ...5 Wiring diagram FS2MIF 141AE2 FS2MIF 181AE2 FS3MIF 211AE2 FS3MIF 271AE2 8 ...
Page 9: ...FS4MIF 281AE2 FS4MIF 361AE2 9 ...
Page 10: ...FS5MIF 421AE0 10 ...
Page 33: ...9 3 1 2 Indoor outdoor units communication error ...
Page 41: ...9 3 3 2 Communication malfunction between IPM board and outdoor main board ODU E3 ...
Page 44: ...9 3 3 5 High pressure protection ODU P1 For FS4MIF 281AE2 FS4MIF 361AE2 FS5MIF 421AE0 ...
Page 46: ...9 3 3 7 Current protection of compressor ODU P3 ...