background image

19

Each valve and air shutter is individually tested and adjusted prior to shipment. Normally adjustment is not required, however, 
vibration during transit, gas conversion or variations in the local gas supply may make minor adjustments  necessary. 
Check for the proper burner flame characteristics and adjust air shutters if necessary. Burner flames should be blue and stable 
with no yellow tips, excessive noise or lifting of the flame from the burner. If any of these conditions exist, check that the air 
shutter or burner ports are not blocked.
If the condition persists, adjust the air shutter as below: 

 

z

If the flame is too yellow, indicating insufficient air loosen the shutter to increase air inlet. 

 

z

If the flame is noisy or tends to lift away from the burner, indicating too much air, tighten the shutter to reduce air.

air shutter

 

z

Make sure all oven and burner knobs are set to 

OFF

 before connecting range 

to gas supply. 

 

z

After final gas connection is made, turn gas supply on and test all connections in 
gas supply piping for gas leaks with a soapy water solution. 

 

z

In order to avoid property damage or serious personal injury, never use a Iighted 
match or open flame.  
If a leak is present, tighten joint or unscrew, apply more joint compound, tighten 
again and retest connection for leak.

ON

GAS

COOKTOP BURNERS 

LEAK TESTING

 

z

To check that the ignition system operates correctly, light each burner by itself, then all 
burners in combination.

 

z

Check for a well-defined blue flame without any yellow tipping.

 

z

If any abnormality is evident, check that the components of the burner assembly are 
located properly.

 

z

When installing the burner port ring, align the two locating pins in the bottom side of 
the port ring with the locating notch and center holes on the top side of the simmer 
ring, and make sure these are properly engaged.

 

z

Incorrect installation may produce a potentially dangerous flame and result in poor 
burner performance.

 

z

No air shutter adjustment is possible on the cooktop burners. Proper operation is 
achieved with factory installed settings for the correct gas type.

 

z

If proper operation cannot be obtained, contact Customer Care or your nearest 
Fisher & Paykel Authorized Service Center. 

 

z

The range and cooktop must not be used by the customer until proper operation 
has been achieved.

GRILL AND GRIDDLE BURNERS (SOME MODELS ONLY) 

lifting off

stable blue flame

yellow tip

Summary of Contents for RDV3-304

Page 1: ...RDV3 304 RIV3 304 RDV3 366 RIV3 365 RDV3 488 RDV3 485GD RHV3 484 RDV3 486 models PROFESSIONAL RANGE INSTALLATION GUIDE US CA...

Page 2: ...any electrical switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier cal...

Page 3: ...may result in damage or personal injury Proper equipment and adequate manpower must be used in moving the range to avoid personal injury or damage to the unit or the floor The unit is heavy and rests...

Page 4: ...ian The electrician should also check that the socket cable section is suitable for the electricity drawn by the range z Service should only be done by authorized technicians Technicians must disconne...

Page 5: ...5 10 x 2 wood screws 4 Anti tip bracket 1 5 16 x 1 1 2 sleeve anchors 2 Lag bolts and washers 2 Foot cover sets 2 PARTS SUPPLIED FOR INSTALLATION...

Page 6: ...from rear of chassis to front of control panel 27 11 16 703 F Height from top of cook surface to top of pan supports 1 9 16 40 G Height from top of cook surface to top of z vent trim as illustrated z...

Page 7: ...from rear of chassis to front of control panel 27 11 16 703 F Height from top of cook surface to top of pan supports 1 9 16 40 G Height from top of cook surface to top of z vent trim as illustrated z...

Page 8: ...from rear of chassis to front of control panel 27 11 16 703 F Height from top of cook surface to top of pan supports 1 9 16 40 G Height from top of cook surface to top of z vent trim as illustrated z...

Page 9: ...Guidance dimension only Combustible covering for a ventilation hood and non combustible surface clearances are governed by local codes rather than these dimensions Non combustible surfaces as defined...

Page 10: ...Combustible RANGE RANGE MOUNT LOW BACKGUARD WALL MOUNT HIGH BACKGUARD LOW SHELF WALL MOUNT HIGH BACKGUARD HIGH SHELF BACKGUARD WIDTH INCHES MM 30 models BGRV2 1230 BGRV2 3030 BGRV3 3030H 29 7 8 759 3...

Page 11: ...hoods and blowers are designed for use with single wall ducting however some local building codes or inspectors may require double wall ducting and or a damper Consult local building codes and or agen...

Page 12: ...the two shipping bolts made visible by removing the lower guard Holding the door on both sides lift door back up to 45 and carefully pull the door out and away from the hinges Before restraining the p...

Page 13: ...the door out and away from the hinges Open the hinge locks fully on both sides Open the door completely Holding the door at 45 carefully align the hinge tongues with the hinge slots Push the door in u...

Page 14: ...ator location may vary depending on model SUPPLY AREA DIMENSIONS RIV3 MODELS IN MM A Distance from either edge of range to supply area 1 1 2 38 B Height of electrical supply area from floor 6 152 C De...

Page 15: ...z Observe all governing codes and ordinances when grounding In the absence of these codes or ordinances observe National Electrical Code ANSI NFPA No 70 current issue See the following information in...

Page 16: ...ng for the unit is to be brought into the terminal block through the conduit and through the strain relief The ends of the wiring must have 1 4 faston closed loop lugs attached Make suitable connectio...

Page 17: ...edition of National Fuel Gas Code ANSI Z 223 1 Warning this appliance must be installed by a licensed plumber or gas fitter when within the Commonwealth of Massachusetts z A manual shut off valve supp...

Page 18: ...the height Long hem edge z Ensure the doors and toe kick panel are securely in place if removed previously z Ensure any backguard is fitted prior to final positioning Refer to Backguard considerations...

Page 19: ...ty damage or serious personal injury never use a Iighted match or open flame If a leak is present tighten joint or unscrew apply more joint compound tighten again and retest connection for leak ON GAS...

Page 20: ...te drill x2 5 16 diameter pilot holes in the center of the larger holes to a depth of at least 1 3 4 3 Place the sleeve anchors into the holes and use a hammer to tap them all the way in 4 Tighten the...

Page 21: ...as shut off valve installed in an accessible location F Unit tested and free of gas leaks ELECTRICAL F Receptacle with properly rated over current protection is provided for service cord connection F...

Page 22: ...ge at any time The product specifications in this guide apply to the specific products and models described at the date of issue Under our policy of continuous product improvement these specifications...

Reviews: