FISCHER DE44 Operating Manual Download Page 4

 

 

Commissioning  

All electrical supply, operating and measuring lines, 
and the pressure connections must have been cor-
rectly  installed  before  commissioning.  All  supply 
lines are  arranged so  that  there  are no mechanical 
forces acting on the device. 

Check  that  the  pressure  connections  do  not  leak 
before commissioning. 

5.1 

Display 

 

 

 

 

• 

The  3.5  digit  LCD  display  represents  the  cur-
rent differential pressure in normal mode.  

• 

The  selected  measuring  unit  is  illuminated  on 
the right of the display.  

 

The  units  shown  in  the  picture  may  vary  from 
the actual model. 

• 

Two light diodes 

 and 

 above the display in-

dicate  the  status  of  the  switching  outputs.  As 
soon  as  the  switch  is  closed,  the  respective 
LED shines. 

• 

On  the  left  side,  P1  and/or  P2  show  which 
channel is currently being displayed. 

When the parameters are being set, the display ei-
ther shows the respective menu item or the associ-
ated  parameter  value.  The  device  continues  to 
function  whilst  the  parameters  are  being  set;  apart 
from  two  exceptions,  the  changes  come  into  effect 
instantly.  

The  exceptions  are  firstly  a  change  of  switching 
times 

–  here,  the  previously  valid  time  needs  to 

have ended and a change to the support point table 
(see  5.3.8  or  5.3.9).  Here  all  output  signals  and 
switching  states  are  frozen  until  the  changes  have 
been completed. 

5.2 

Operating keys 

The operating keys have the following function: 

ÿ 

Page down menu 
Reduce value 

û 

Enter key 

þ 

Page up menu 
Increase value 

5.3 

Configuration 

For  commissioning  there  is  a  multitude  of  setting 
options for optimum adaptation of the device to the 
measuring point and task at hand. This section co-
vers these options step by step. 

Depending on the device model 

1

 some menu items 

may not be available. For example, all characteristic 
curve functions are faded out in the menu if the de-
vice does not have a signal output. 

It is possible to completely configure the 
device  using  a  PC  adapter  at  the  PC. 
Here  all  parameters  are  directly  visible 
and accessible. Also, the entire configu-

ration  can  be  loaded,  saved  and  documented  as  a 
printout.  For  more  information  about  this  program, 
please  refer  to the  program  documentation  (cf.  Ac-
cessories). 

5.3.1 

General points 

Connect the device to the power supply and ensure 
that  it  is  not  under  any  pressure  (if  necessary,  dis-
connect any pressure lines). 

Proceed as follows to set a parameter: 

• 

Press  the  enter  key 

û

  to  switch  to  the  menu. 

ESc 

will appear on the display. 

• 

Use  the  arrow  keys 

ÿ

 

þ

  to  select  a  parameter 

from the list. 

• 

Press the enter key 

û

 to call up the parameter. 

• 

Use the arrow keys 

ÿ

 

þ

 to set the required val-

ue. 

• 

Press the enter key 

û

 to save the value. 

After setting all parameters, leave the menu as fol-
lows:

2

 

• 

Use the arrow keys 

ÿ

 

þ

 to set the 

ESc

 parame-

ter.  You  will  find  these  at  the  start  and  also  at 
the end of the list of parameters. 

• 

Press the enter key 

û

 to leave the menu. 

5.3.2 

Selecting the pressure unit 

First  select  the  pressure  measuring  unit.  The  unit 
that is currently valid is illuminated to the right of the 
number  displays.  Press  the  middle  key 

û

  to  make 

the  setting  and  then  search  for  the  parameter 

EIN

 

using  the  right-hand  key 

þ.

  Press 

û

  again  an  then 

change the displayed value using 

þ

 or 

ÿ

.  

1 = top 
2 = middle 
3 = bottom 

                                                      

1

 with regard to the transmitter signal, voltage output, current 

output, etc. 

2

  All set parameter values are only valid once you leave the 

menu via the 

ESC

 parameter. 

Switching output 1 

Switching output 2 

3.5 character LED display 

Operating keys 

Measuring unit 

Channel no. 

Summary of Contents for DE44

Page 1: ...zed personnel familiar with the in stallation commissioning and operation of this product Specialized personnel are persons who can assess the work they have been assigned and recognize potential dang...

Page 2: ...eed between the manufacturer and user 3 Description of the product and func tional description 3 1 Function diagram 3 2 Design and mode of operation The device is based on two piezo resistive sensor e...

Page 3: ...ilters need to be installed at suitable points The pressure sensing lines need to be kept as short as possible and installed without sharp bends to avoid interfering delay times If the pressure sensin...

Page 4: ...tions step by step Depending on the device model 1 some menu items may not be available For example all characteristic curve functions are faded out in the menu if the de vice does not have a signal o...

Page 5: ...isplay output signal and switch points but not on the measuring cell it self This parameter can be used to set the reaction time to the pressure jumps The value range is 0 0 s to 100 0 s But with maxi...

Page 6: ...means of hydrostatic pressure measure ments are two typical examples of this In these cases you might want to change the output signal of the transmitter to a non linear characteristic curve so that t...

Page 7: ...ue 000 cancels the password function If a password has been issued the text PAS appears after ESc and and you need to enter the correct value using and You will only arrive at all other menu items aft...

Page 8: ...e of the de vice can be shown sensibly MA Start of measuring range The measuring value is set in that the output signal is minimal e g 0V 0mA or 4mA ME End of measuring range The measuring value is se...

Page 9: ...must not be exposed to mechanical shocks It shall be transported only in packaging specifically intended for transport 8 Service All damaged or faulty devices shall be directly sent to our repair depa...

Page 10: ...4 20 mA 0 10 V DC Admissible apparent ohmic resistance RL Ub 4 V 0 02 A Ub 26V RL 1100 Ub 26V RL 2 K Ub 15V RL 10 K Ub 12 15V Characteristic curve can be programmed Power consumption approx 2 W VA Di...

Page 11: ...ith 3 30 support points Password 001 999 000 no password protection Comments 0 For values from 0 2 the display switches between dP1 and dP2 rhythmically 1 Measuring values around zero are set to zero...

Page 12: ...5 6 0 40 mbar 5 7 0 60 mbar 5 8 0 100 mbar 5 9 2 5 2 5 mbar A 6 4 4 mbar A 7 6 6 mbar A 8 10 10 mbar A 9 16 16 mbar B 1 25 25 mbar B 2 40 40 mbar C 5 60 60 mbar B 3 100 100 mbar B 4 0 400 Pa D 7 0 60...

Page 13: ...40 mbar 5 7 0 60 mbar 5 8 0 100 mbar 5 9 2 5 2 5 mbar A 6 4 4 mbar A 7 6 6 mbar A 8 10 10 mbar A 9 16 16 mbar B 1 25 25 mbar B 2 40 40 mbar C 5 60 60 mbar B 3 100 100 mbar B 4 0 400 Pa D 7 0 600 Pa D...

Page 14: ...sured value display contact elements 3 1 2 digit LED 2 relay contacts 3 3 1 2 digit LED 2 semiconductor switches 6 Electrical connection M12 plug connection M Assembly option Standard attachment boreh...

Page 15: ...14 Declaration of Conformity...

Page 16: ...ject to change without notice Changements techniques sous r serve Fischer Mess und Regeltechnik GmbH Bielefelder Str 37a D 32107 Bad Salzuflen Tel 49 5222 9740 Fax 49 5222 7170 eMail info fischermesst...

Reviews: