FISCHER DE44 Operating Manual Download Page 11

 

11.1  Programming 

Programming is carried out via the membrane keypad and menu navigation; can be locked with a password 

 

Settings 

Attenuation 

0.0 ... 100.0 s (jump response time 10 / 90 %) for signal output; separately also for display 

Selection of the displayed measuring 

value 

0.0 = only differential pressure 1 (dP1) 
0.1 = only differential pressure 1 (dP1) 
0.2 …25.5 = switchover time in seconds, dP1 and dP2 alternately 

(0)

 

Switching output 1 / 2 

Switch-off point, switch-on point, response time (0...100s), function (NC / NO contact) 

(4)

 

Measuring range unit 

mbar / Pa / "fee unit", starting value, end value and decimal point for "free unit" 

Zero-point stabilising 

0 ... 1/3  of the basic measuring range 

(1)

 

Output signal 

User-definable within the basic measuring range 

(2) (4)

 

Zero point correction 

± 1/3 of the basic measuring range 

(3)

 

Implementation of characteristic curve 

linear, square rooted, flat cyl. tank, table with 3...30 support points  

Password 

001 ... 999 (000 = no password protection) 

Comments: 
(0):  For values from 0.2, the display switches between dP1 and dP2 rhythmically. 
(1):  Measuring values (around zero) are set to zero. (e.g. to suppress seepage). 
(2):  Maximum effective spread 4:1. Only the output signal is influenced. This in turn enables a decreasing characteristic curve,  
 

if the start of the measuring range > end of the measuring range. 

(3):  Zero point correction for compensation of various installation positions. 
(4) 

Differential pressure 1 (dP1) controls switching output 1 and the output signal 

 

Differential pressure 2 (dP2) controls switching output 2 

 

12  Dimensional drawings 

 

 

(all dimensions in mm unless otherwise specified) 

Wall mounting plate 
(optional) 

Rear view  

without wall mounting plate 

M12 plug connection 

Hose screw connection 
 for 6 or 8 mm hose 

Bore-holes for  

tapping screws Ø 3.5 

Connector 1 

1   (-) Power supply  br 
2   - Signal 

ws 

3   - Power supply 

bl 

4   + Signal 

sw 

5   n.c. 

 

Connector 2 

1   Switch contact 1  br 
2   Switch contact 2  ws 
3   Switch contact 2  bl 
4   Switch contact 1  sw 

bridged internally 

Coding A 

Summary of Contents for DE44

Page 1: ...zed personnel familiar with the in stallation commissioning and operation of this product Specialized personnel are persons who can assess the work they have been assigned and recognize potential dang...

Page 2: ...eed between the manufacturer and user 3 Description of the product and func tional description 3 1 Function diagram 3 2 Design and mode of operation The device is based on two piezo resistive sensor e...

Page 3: ...ilters need to be installed at suitable points The pressure sensing lines need to be kept as short as possible and installed without sharp bends to avoid interfering delay times If the pressure sensin...

Page 4: ...tions step by step Depending on the device model 1 some menu items may not be available For example all characteristic curve functions are faded out in the menu if the de vice does not have a signal o...

Page 5: ...isplay output signal and switch points but not on the measuring cell it self This parameter can be used to set the reaction time to the pressure jumps The value range is 0 0 s to 100 0 s But with maxi...

Page 6: ...means of hydrostatic pressure measure ments are two typical examples of this In these cases you might want to change the output signal of the transmitter to a non linear characteristic curve so that t...

Page 7: ...ue 000 cancels the password function If a password has been issued the text PAS appears after ESc and and you need to enter the correct value using and You will only arrive at all other menu items aft...

Page 8: ...e of the de vice can be shown sensibly MA Start of measuring range The measuring value is set in that the output signal is minimal e g 0V 0mA or 4mA ME End of measuring range The measuring value is se...

Page 9: ...must not be exposed to mechanical shocks It shall be transported only in packaging specifically intended for transport 8 Service All damaged or faulty devices shall be directly sent to our repair depa...

Page 10: ...4 20 mA 0 10 V DC Admissible apparent ohmic resistance RL Ub 4 V 0 02 A Ub 26V RL 1100 Ub 26V RL 2 K Ub 15V RL 10 K Ub 12 15V Characteristic curve can be programmed Power consumption approx 2 W VA Di...

Page 11: ...ith 3 30 support points Password 001 999 000 no password protection Comments 0 For values from 0 2 the display switches between dP1 and dP2 rhythmically 1 Measuring values around zero are set to zero...

Page 12: ...5 6 0 40 mbar 5 7 0 60 mbar 5 8 0 100 mbar 5 9 2 5 2 5 mbar A 6 4 4 mbar A 7 6 6 mbar A 8 10 10 mbar A 9 16 16 mbar B 1 25 25 mbar B 2 40 40 mbar C 5 60 60 mbar B 3 100 100 mbar B 4 0 400 Pa D 7 0 60...

Page 13: ...40 mbar 5 7 0 60 mbar 5 8 0 100 mbar 5 9 2 5 2 5 mbar A 6 4 4 mbar A 7 6 6 mbar A 8 10 10 mbar A 9 16 16 mbar B 1 25 25 mbar B 2 40 40 mbar C 5 60 60 mbar B 3 100 100 mbar B 4 0 400 Pa D 7 0 600 Pa D...

Page 14: ...sured value display contact elements 3 1 2 digit LED 2 relay contacts 3 3 1 2 digit LED 2 semiconductor switches 6 Electrical connection M12 plug connection M Assembly option Standard attachment boreh...

Page 15: ...14 Declaration of Conformity...

Page 16: ...ject to change without notice Changements techniques sous r serve Fischer Mess und Regeltechnik GmbH Bielefelder Str 37a D 32107 Bad Salzuflen Tel 49 5222 9740 Fax 49 5222 7170 eMail info fischermesst...

Reviews: