Installation Instructions
Page 64 Panda PMS AGT-DC 4000 - Chapter D: Installation Instructions
Electrical fuses
It is absolutely essential that the electrical system installation is inspected by a qualified electrical
technician. The generator should have its own AC
input electrical fuses
. The fuses should be
sized such that the rated current of the generator on each of the individual phases is not excee-
ded by more than 25%.
Data for gensets with power output greater than 30kW on request!
The fuses must be of the slow type. A 3-way motor protection switch must be installed to protect
the electrical motor.
Required cable cross-sections
The following recommended electrical cable dimensions (cross sections) are the minimum requi-
red sizes for a safe installation.
(see “Cable cross-section” on Page II)