![Fischer Panda Panda AGT-DC 4000 PMS Installation Manual Download Page 63](http://html1.mh-extra.com/html/fischer-panda/panda-agt-dc-4000-pms/panda-agt-dc-4000-pms_installation-manual_2294311063.webp)
Installation Instructions
Panda PMS AGT-DC 4000 - Chapter D: Installation Instructions Page 57
1. Display operating hours
2. Control light - temperature
3. Control light - oil pressure
4. Control light - charge control
5. Control light - operating status
red glowing
Generator is in „Stand-by“-mode
red blinking
Generator is started manually
red blinking for more than 20 seconds
Generator did not start when activated manu-
ally
green blinking
Generator runs in manual mode
green glowing
Generator runs in automatic mode
6. Switch for Manual Start:
• Switch pressure in sleeping mode: Generator is started and the panel switches to manual mode,
i.e. automatic cut off requirements are not carried out.
• Switch pressure in manual mode: If the generator starts automatically, the generator continues
to run and the panel switches to automatic mode, i.e. when the last automatic start cuts out, the
generator stops and the panel goes into sleeping mode; If the generator is not started automa-
tically, the generator stops and the panel goes into sleeping mode.
• Switch pressure in automatic mode: The generator continues to run and the panel switches to
manual mode.
7. Main switch:
If it is already in automatic mode when it is switches on, the generator starts and the panel swit-
ches to automatic mode; If it is not in automatic mode, the panel switches to sleeping mode; If the
generator is switched off, the generator will stop in every case.