Generator Failure
Seite/Page 134 - Kaptitel/Chapter 8: Generator Failure
10.6.16
8.9.1.10 Motor runs in off position.
8.9.1.11 Motor stops by itself.
8.9.1.12 Sooty black exhaust.
8.9.1.13 Generator must be shut off immediately if:
Cause
Solution
Fuel inlet solenoid valve or throttle shut solenoid is not switching off.
Check wire connections to solenoid. Check valve functions as in the
„Inlet Fuel Solenoid Valve“ or in the truckle shut off solenoid sections.
Replace if necessary.
Cause
Solution
Lack of fuel.
Check fuel supply system.
Excess heat in cooling system (thermo switch tripped)-lack of cooling
water. Is indicated on the remote control panel.
Check cooling water system flow: water pump, inlet water filter, extra
heat exchanger coolant flow.
Lack of ill pressure sensor tripped). Is indicated on the remote control
panel.
Check oil-level and if necessary top up.
Check motor's oil-pressure and have repaired by motor manufacturer-
Service if necessary.
Over-/under voltage. Is indicated on the remote control panel.
Switch-off the remote control panel, reduce the electrical load (switch-off
load), start again.
Cause
Solution
Generator is overloaded.
Check electrical load and switch off unnecessary load.
Insufficient intake air.
Check intake air filter; clean if necessary.
Fuel injector faulty.
Replace injector.
Valve clearance incorrect.
Readjust valve clearance to correct value (refer to motor-manual).
Poor fuel quality.
Use better quality diesel (recommended: 2-D Diesel).
Poor combustion.
Incorrect AFR (air/fuel ratio) due to motor timing adjustment. Have motor
serviced by manufacturer.
Low compression pressure.
See motor-manual.
Cause
Solution
- motor rpm suddenly rises or drops
- unusual noise comes from genset
- exhaust colour suddenly becomes dark
- leakage in the cooling water system.
Refer to respective section of manual and if necessary, have repaired by
motor manufacturer-Service, or Panda representative.
Summary of Contents for 12000x PVMV-N
Page 10: ...Seite Page 10 Kapitel Chapter 1 10 6 16 Leere Seite Intentionally blank ...
Page 96: ...Installation Instructions Seite Page 96 Kaptitel Chapter 5 Installation Instructions 10 6 16 ...
Page 148: ...Seite Page 148 Kapitel Chapter 9 Appendix 10 6 16 Leere Seite Intentionally blank Appendix ...
Page 149: ...Panda_xControl_eng R01 5 10 6 16 Panda xControl Manual ...
Page 189: ...Panda xControl 10 6 16 Kapitel Chapter 11 Panda xControl Seite Page 189 ...