Generator Failure
Seite/Page 130 - Kaptitel/Chapter 8: Generator Failure
10.6.16
Fig. 8.8.1-1: Generator termination box
Initializing the magnetic field in the windings through
external current from a 4,5 - 9 volt battery. (No car-
battery!)
8.8.2 Stop solenoid
There are two different variations:
A. Energized to stop
By pressing the „OFF“-button on the remote control panel the stop solenoid is supplied with voltage and operate,
through this the injection nozzles resets to zero position and the generator stops.
B. Energized to run
This version is equipped with two solenoids an actuating and a stop solenoid. After being fed with current, the
actuating solenoid attracts the adjusting lever of the fuel injection pump, through which the fuel can flow. The
actuating solenoid is switched off once the final position has been reached, which is maintained by the stop solenoid
for as long as the generator is running
.
Notice!:
When starting the „START“-button may not be pressed
longer than 5 sec., because the stop solenoid pulls too
much current over the starter. Otherwise the stop
solenoid must be disconnected.
Fig. 8.8.2-1: Stop solenoid
Stop solenoid (optional)