background image

12

£

WARNING: The minimum pilot test must be accomplished by a trained and qualified burner

technician.

Minimum Pilot Test

This test insures that the flame detector will not sense a pilot flame too small to light the main flame
reliably. It must be made on every new installation as well as following the repositioning of the flame
detector. 

This procedure should not be used on a direct spark ignited burner.

1.

Manually shut off the fuel to the main burner.

2.

Connect a test meter to the test jacks on the Amplifier Module.

3.

Initiate a normal startup.

4.

Reduce the fuel to the pilot until the DC voltmeter reads 3.5 volts for UV scanners. See WARN-

ING below. This is the minimum pilot. For flame rectification the flame signal for minimum
pilot varies depending on the application. See WARNING below.

5.

Slowly turn on the main fuel and insure that the main flame lights off promptly and normally.

WARNING: If light off is delayed, shut off the power to the installation. Realign the flame

detector so that pilot flame detection requires a larger pilot flame. Repeat this test until the

main flame lights reliably with minimum pilot.

6.

After the minimum pilot test is completed satisfactorily, increase the pilot flame to normal size,
and observe that the main flame is properly established during a normal cycle.

Flame Failure Test

1.

Temporarily connect spark ignition and pilot valve to Terminal #3.

2.

Initiate a normal startup.

3.

Manually shut off all fuel and observe the loss of flame signal on the test meter.

4.

If flame signal does not reduce to zero within the flame failure response time of the control

(F.F.R.T. determined by selection of amplifier), verify that the UV flame detector is not actuated
by the spark. If spark is detected, a metallic shield or relocation of the UV detector sight pipe is

required.

5.

IMPORTANT:

 When the test is completed, reconnect the spark ignition to Terminal #4.

Recommendation

Periodic Safety Check: 

Test the complete flame safeguard system at least once a month. This test

should verify flame failure safety shutdown and positive fuel cutoff when the fuel valve is de-ener-
gized.

Replaceable Fuse

The programmer modules are designed with a field replaceable fuse. The fuse is located on the
printed circuit board near the connectors. In the event the fuse becomes shorted, the Operating Con-
trol, Air Flow, and PTFI LED’s will light. However, KL or KF (see WIRING ARRANGEMENTS -
later in this document) will not be energized and the control will lock out. The fuse will blow as a
result of an overload condition on Terminals 3, 4, or 5. To replace the fuse, remove the fuse (using a
small screwdriver) and install a Fireye replacement fuse (P/N 23-176) or equivalent 2AG, 8 amp fuse
Type Fast-Acting (e.g. Little Fuse #225008).
Order Fireye replacement fuse P/N 23-183 or equivalent (3.5 amp fuse 2AG Type SLO-BLO) for
programmer modules used with the MC230 and MC230R chassis (e.g. Little Fuse #22903.5).

Summary of Contents for M-SERIES II

Page 1: ...e are deter mined by the programmer module Type of flame scanner UV or Flame Rod and Flame Failure Response Time F F R T are determined by the amplifier module LED indicator lights on all programmer m...

Page 2: ...125 VA pilot duty solenoid valve plus 250 VA Transformer 5 Main Fuel Valve s 125 VA pilot duty solenoid or 25 VA pilot duty solenoid and 400 VA opening motorized 8 Motor or contactor Motor normally e...

Page 3: ...TRAIGHT FEMALE PIPE THREAD 1 DIA 25 4 UV1A UV SCANNER 36 FLEXIBLE CABLE UV1A3 72 FLEXIBLE CABLE UV1A6 2 50 8 36 1m APPROX FLEXIBLE CABLE 3 8 PIPE THREAD 13 16 DIA 206 UV2 UV SCANNER 2 3 8 60 3 1 3 16...

Page 4: ...he following Chassis UV Scanner or Flame Detector Programmer Module Wiring Base Amplifier Module WARNING Installer must be trained and qualified Follow the burner manufacturer s instructions if suppli...

Page 5: ...b a window coupling Fireye part 60 1257 to seal off furnace or burner pressure c cooling air to reduce the scanner sight pipe temperature 3 Mount rigidly a short length 10 20cm of 1 2s or 3 4s black...

Page 6: ...Scanner Installations Wiring of UV Scanners The UV1A scanner is supplied with 3 90cm or 6 180cm of flexible cable The UV 2 scanner is supplied with 3 90cm of flexible cable If it is necessary to exte...

Page 7: ...e from the side so as to safely prove an adequate pilot flame under all draft conditions 4 If the flame is nonluminous air and gas mixed before burning the electrode tip should extend at least 1 2s 12...

Page 8: ...30M Maximum wiring run not to exceed 400 feet 120M MAINTENANCE Type UV1 UV2 UV8A and 45UV3 Ultraviolet Scanners The viewing area of the scanner must be kept clean Even a small amount of contamination...

Page 9: ...is energized only during the Ignition Safety Time Flame On This LED is energized whenever a flame signal is detected by the UV scanner or Flame detector Alarm this LED is energized whenever a safety...

Page 10: ...ition is initiated PTFI LED lit 3 When main flame is detected Flame LED lit KF 1 closes energizing Terminal 5 which pow ers the secondary main fuel valve if used KF 2 opens de energizing Terminal 4 wh...

Page 11: ...for flame rectification amplifiers 5 Inadequate flame signal may be improved by a Assuring that the flame detector and wiring installations have followed the instructions on Pages 5 through 9 b Assuri...

Page 12: ...gnition and pilot valve to Terminal 3 2 Initiate a normal startup 3 Manually shut off all fuel and observe the loss of flame signal on the test meter 4 If flame signal does not reduce to zero within t...

Page 13: ...clean Use a clean cloth with detergent as often as oper ating conditions require Remove any residual detergent ROTATION It is recommended that units purchased as spares be rotated periodically so tha...

Page 14: ...NG SUCCESSFUL RESET REPLACE PROGRAMMER DID FLAME LED COME ON YES MP100 4 7 SECONDS MP230 PREPURGE DELAY TIME NO YES NORMAL LOCKOUT NO NO NO NO NO YES AMPLIFIER DEFECTIVE OR MC120 REPLACE SCANNER REPEA...

Page 15: ...IN BURNER NO TROUBLESHOOTING TIPS 1 Verify that there is a solid earth ground wire brought to the panel that the Fireye base is mounted to 2 In a rectification system verify that terminal S1 is solidl...

Page 16: ...ME ROD FUEL VALVE CHASSIS WITH MART3 OR MART1T AMPLIFIER MODULES IGNITION GAS VALVE CONNECTION TO TERMINAL 1 IS NOT REQUIRED WITH MART3 OR MART1T AMPLIFIER MODULE WITH MAUV3 AND MAUV1T KB ENERGIZED WH...

Page 17: ...DDED TO REQUIRE OPERATOR START UP EACH TIME THE BURNER FIRES S2 3 5 4 1 IGNITION 7 8 2 A 6 PILOT S1 B MULTIPLE BURNER SYSTEMS S2 3 5 4 1 IGNITION 7 8 2 A 6 PILOT S1 LIMIT R MANUAL RESET MAIN GAS VALVE...

Page 18: ...ted in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replace ment or repair...

Reviews: