8
INSTALLATION PROCEDURE
Wiring Base
Mounting of the base can be accomplished with 2 screws. The recommended screw sizes are #10
PAN HD x 5/8inch (5mm PAN HD x 16mm) and #10 PAN HD x 3/8 inch (5mm PAN HD x 10mm).
Refer to Figure 2 for mounting dimensions.
Grounding Wire
Each BurnerPRO control is fitted with a grounding wire. Attach the open end of the grounding wire
to a ground terminal on the wiring base (see figure 2 below). Undo the screw terminal with a screw-
driver and place the ground lug over the terminal. Re-install the screw over the ground lug. Do not
attach the grounding wire to a Neutral (N) terminal.
FIGURE 2.
Note: The location should be free from excessive vibration and within the ambient temperature rating.
4.20
4.20
3.15
3.15
.53
.53
1
12
24
13
MOUNTING HOLE LOCATIONS
1.22
OUTER KNOCK OUT
AREA IS FOR 1/2 NPT
TYPICAL 4 PLACES
INNER KNOCK OUT
AREA IS FOR 16MM
TYPICAL 4 PLACES
1
12
13
24
NOT GROUNDED
CONNECT TO GROUND
NOTICE:
Installation, setup, and commissioning of the BurnerPRO control must be done by
's and don’ts of the
trained personnel. The personnel must know the do
authorized and
particular burner and must have relevant experience in the theories and practices of combustion
control. Fireye cannot accept any liability for any consequences resulting from inappropriate,
negligen
t
or incorrect installation, commissioning or adjustment of operating parameters
of the
equipment. BurnerPRO does not have any user serviceable parts. If the unit has a problem,
return the unit to your local distributor, or contact Fireye directly.