BURNERLOGIX SPECIFICATIONS
Supply Voltage:
YB110
120 VAC (+10%, -15%) 50/60 Hz
YB230
230 VAC (+10%, -15%) 50/60 Hz
Power Consumption:
25 VA
Temperature Rating:
-40°C (-40°F) to +60°C (140°F)
Protection Category:
YB110 (YB230)
control NEMA 1 (IP01)
Display, remote mounted NEMA 4X (IP66)
Unit Dimensions:
Wiring base 60-2810-1 - 4.0" (101 mm) W x 5.0" (127mm) H
Wiring base 60-2812-1, 60-2814-1 - 4.0" (101 mm) W x 7.0" (178 mm) H
Shipping Weight:
YB110 (YB230)
Approx. 3.2 lbs. (1.45kg)
OPERATING TEMPERATURE LIMITS
LOAD RATINGS:
CONTROL
MAXIMUM
MINIMUM
YB110, YB230
140°F
60°C
-40°F
-40°C
YP Programmers
140°F
60°C
-40°F
-40°C
BLV512, VFD Display
140°F
60°C
-40°F
-40°C
BLL510, LCD Display
140°F
60°C
-4°F
-20°C
Scanner UV1A, UV2, UV8A, UV90, 45UV3
200°F
93°C
-40°F
-40°C
45UV5-1005, 45UV5-1105
45UV5-1007, 45UV5-1009
55UV5-1007, 55UV5-1009
200°F
93°C
-40°F
-40°C
48PT2
140°F
60°C
-40°F
-40°C
Flame Rod (Tip 2460°F)
1500°F
816°C
-40°F
-40°C
Humidity: 90% R.H. (Non-condensing)
Terminal
Typical Load
A. Maximum Rating
@120V-50/60 Hz
B. Maximum Rating
@230V-50/60 Hz
C. Alternate Rating
M
Burner/Blower Motor
9.8 F.L.A. *
58 L.R.A.
4.0 F.L.A. *
20 L.R.A.
240 VA Pilot Duty
(Motor Starter Coil)
10-11-12-X
Modulator
125 VA Pilot Duty
A
Alarm
50 VA Pilot Duty
Terminal ratings may be selected from either column A or C for 120 VAC or from either column B or C for 30 VAC:
(select the rating from the column which best applies to the connected load on that terminal).
* F.L.A. = full load amps; L.R.A = locked rotor amps