4
FIGURE 2.
Wiring Connections for ED610 and ED510 Remote Display
WIRING FOR E500 COMMUNICATION INTERFACE
See Figure 3. Use an ED610 multi-port connector for each Flame-Monitor or E340 Boiler Control
unit connected in a multi-drop wiring configuration to the E500 Communication Interface. A two (2)
conductor, 22 gage, low capacitance shielded cable (Belden 8761 or equivalent) must be used
between the E500 Communication Interface and each ED610 multi-port connector and E340 Boiler
Control. An ED512 cable is required between the ED610 and the Flame-Monitor. A ferrite core is
provided on the ED512 cable to improve the electrical noise immunity of the FLAME-MONITOR
system.
The connector nearest to the ferrite core must be plugged into the EP Programmer.
MAKE SURE THE FLAME-MONITOR SYSTEM IS PROPERLY GROUNDED. REFER
TO THE WARNING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY
GROUNDED.
Ground the shield at one end only of each individual wiring run. Total maximum cable distances
shall not exceed 4,000 feet.
NOTE: Cable should be routed within the cabinet so that it doesn’t come in close proximity with
ignition wires, high energy contactors or solenoids.
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
ED510 REMOTE
E110 FLAME-MONITOR
ED580-2, -4, -8
ED580-2, -4, -8
8 CONDUCTOR TSP
BELDEN 9554
ED580-2, -4, -8
TO RJ45 CONNECTOR
ON EP/EPD PROGRAMMER
FLAME ON
ED510 DISPLAY MODULE
MOUNTED LOCALLY
FLAME ON
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
9554
1 - RED
1 - BLACK
2 - RED
2 - BLACK
3 - RED
3 - BLACK
4 - RED
TERMINAL CONNECTIONS ON ED610
CONNECT CABLE SHIELD TO TERMINAL 8
ON ONE ED610 ONLY
NOTE: To disable the reset function on
the remote display, move the jumper
on EITHER ED610 multi-port connec-
tor from position 1-2 to position 2-3.
1
2
3
J4
J2
J2
DISPLAY MODULE
1
2
3
4
5
6
7
1
2
3
4
5
6
7
BELDEN CABLE
9554 HAS
4 TWISTED
PAIRS, EACH
PAIR COLOR
CODED RED
AND BLACK.
E110
ED510
FERRITE
CORE