6
FIGURE 4.
Wiring for Modbus Protocol
WIRING FOR REMOTE RESET
A remote reset button can be added when using the ED610 multi-port connector. Wire a normally
open momentary push button across terminals 8 & 4 on the ED610. Jumper J4 must be in position 1-
2. Refer to Figure 6.
REFER TO “CAUTION” FOR REMOTE RESET ON PAGE 3.
FIGURE 5.
ED610 DIMENSIONS
FIGURE 6:
WIRING FOR REMOTE RESET
The ED611 multi-port connector provides for remote reset at the terminal block, but inhibits the
lockout reset capability at the ED510. This is useful for applications that may want to use a key lock
switch in lieu of the reset button located on the ED510 display. Connect the E110 and ED510 as
shown using the ED580 cables. Wire a normally open momentary push button switch across termi-
nals 8 & 4. Jumper J4 on the ED611 must be in position 1 to 2. Refer to Figure 8.
REFER TO “CAUTION” FOR REMOTE RESET ON PAGE 3.
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
E110
OPTION 1 TO PC, PLC, ETC.
ED512-2, -4, -8
FLAME-MONITOR
BELDEN 8761
E110
ED512-2, -4, -8
FLAME-MONITOR
CLEAR
BLACK
TO RJ12 (4P4C) CONNECTOR
ON EP/EPD PROGRAMMER
TO RJ12 (4P4C) CONNECTOR
ON EP/EPD PROGRAMMER
J2
J2
FERRITE
CORE
FERRITE
CORE
EC485
RS485 TO
RS232
CONNECTOR
RS485
OPTION 2
TO CONTROL
SYSTEM
B
A
OR
B
A
SEE FIG. 7
1
2
3
4
5
6
7
8
9
10
1
2
3
J1
J2
J5
J4
H1
H2
ED610
J3
A B
2.00
1.00
2.4
3.00
76.2
50.8
60.9
25.4
E110
ED580 -2, -4, -8
FLAME-MONITOR
TO RJ45 CONNECTOR ON
EP/EPD PROGRAMMER
FERRITE
CORE
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
J2
MOMENTARY CONTACT CLOSURE
J4
1
2