3
®
FIGURE 1.
INSTALLATION AND MOUNTING DIAGRAM OF ED510 WITH 129-145
WIRING CONNECTIONS FOR ED610 AND ED510 REMOTE DISPLAY
See Figure 2. Use the ED610 multi-port connector to remote mount the ED510 display greater than
eight (8) feet away from the Flame-Monitor control. An eight (8) conductor, 18 gage, low capaci-
tance, overall shielded cable (Belden 9554 or equivalent) must be used between the ED610 at the
burner site and the ED610 at the remote site. An ED580 cable is required between the ED510 dis-
play module and the ED610 connector as well as the ED610 connector and FLAME-MONITOR
control. A ferrite core is provided on the ED580 cable to improve the electrical noise immunity of
the FLAME-MONITOR system.
The connector nearest to the ferrite core must be plugged into
the EP Programmer.
MAKE SURE THE FLAME-MONITOR SYSTEM IS PROPERLY GROUNDED. REFER
TO THE WARNING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY
GROUNDED.
The position of the ferrite core is not critical on the ED580 cable connected between the ED510 dis-
play and ED610 adapter. The Flame-Monitor control will drive two (2) ED510 display modules.
The Belden cable 9554 has 4 twisted pairs with an overall shield. Conductor pairs are color coded
red and black and numbered at one (1) inch intervals (e.g. 1-black, 2-red). Maximum cable distance
of the ED510 from the Flame-Monitor control is 700 feet. Do not ground shield at both ED610's.
CAUTION: When the remote display or the remote reset is installed, make sure that the
remote location is within sight and sound of the fired equipment. Safety procedures require
that the operator be at the burner to reset the safety controls in order that any unsafe condi-
tions can be discovered and corrected prior to resetting the safety controls or devices. Fireye
does not recommend remote reset locations beyond sight and sound of the burner.
KEYPAD/DISPLAY
FRONT
GASKET
PEM NUT
INSIDE
MOUNTING
SCREW
MOUNTING
PLATE
MAXIMUM THICKNESS
CONNECTOR
CABLE (2’, 4’, or 8’)
TO EP/EPD PROGRAMMER
5/64 INCH (2.0mm) PANEL
3.63
(92.0)
3.63
(92.0)
SUGGESTED PANEL CUTOUT DIMENSIONS