background image

3

IMPORTANT SMOKE ALARM SITING 
AND EXCEPTION INFORMATION:

The best place to put a smoke alarm is on the ceil-
ing. Install a smoke alarm as close to the centre of
the ceiling as possible. If this is not practical, mount
no closer than 30cm from a wall or corner.
Otherwise, if ceiling mounting is very difficult, you
may install smoke alarms on walls, between 15 and
30cm from ceiling/wall intersections, making sure
that the smoke alarm is above the level of any door
openings.

Install ceiling mounted smoke alarms at the highest point in the area at which smoke is likely to collect.

FIGURE 3: Wall Mounting of Smoke Alarms (Small Rooms and Short Hallways)

Site a smoke alarm in each room that is divided by a partial wall (either coming down from the ceiling at
least 20cm or coming up from the floor).

Site smoke alarms on peaked, cathedral, or gabled ceilings
90cm from the highest point (measured horizontally).

Site a smoke alarm in lived-in attics or attics which house electri-
cal equipment like furnaces, air conditioners, or heaters.

Where You Should Not Site Smoke Alarms

Do not site a smoke alarm within close proximity of heating and cooling supply vents or
within close proximity of return or fresh air vents. Smoke may be blown away from the
smoke alarm by the supply vents, or could be diffused or reduced by being diverted into the
return air vent.

Do not site your smoke alarm in an area where the temperature may fall below 5°C, or rise
above 45°C. Smoke alarms are designed to work safely only within these temperature
ranges, and failure to alarm, improper alarms, or nuisance alarms may result from operation
outside these temperature limits.

Do not site a smoke alarm in a damp or very humid area such as bathrooms with showers,
where the normal humidity may rise above 93% relative humidity. Above this level, moisture
may condense inside the smoke chamber and cause false alarms. 

Do not site an ionisation smoke alarm in an area where particles of combustion are normally
present, such as kitchens or garages. An ionisation type smoke alarm with a FALSE ALARM
CONTROL feature or a photoelectric type smoke alarm should be used to minimize nuisance
alarms.

Do not site a smoke alarm in dusty or dirty areas—SUCH AN INSTALLATION CANNOT BE
RELIED UPON. An accumulation of dust and dirt in the sensing chamber may block the
openings and prevent an alarm, or may get inside the alarm and cause false alarms. If a
smoke alarm is required in such an area, vacuum it frequently and test it according to direc-
tions in 

Maintenance and Cleaning

(page 5).

Do not site a smoke alarm in the dead air space in the corner where the wall meets the ceil-
ing. If in doubt as to the exact alarm siting, for your safety, contact your local fire brigade
for help in choosing a location.

Do not site a smoke alarm where bugs or insects are present before eliminating or minimiz-
ing the bug problem. Although all smoke alarms built since 1986 are made to prevent bugs
from entering the detection chamber, bugs may build up on chamber openings and prevent
smoke from entering. As a result, unit should be vacuumed frequently as explained in

Maintenance and Cleaning

(page 5).

Do not site a smoke alarm within close proximity of a fluorescent light. Electrical noise may
cause nuisance alarms.

Do not paint smoke alarm.

Do not install smoke alarms closer than 300mm to light fittings.

Do not install smoke alarms on surfaces that can become very hot or very cold, such as
poorly insulated external walls, or ceilings in houses with a ceiling heating system.

Do not mount a smoke alarm in such a position that it is difficult or dangerous to reach for
maintenance or battery replacement.

Do not site the alarm in an area where water or other liquids may enter the alarm.

90cm

PEAKED CEILING

1m

30cm

15cm

MINIMUM

30cm

MAXIMUM

CEILING

SIDE

WALL

ACCEPTABLE HERE

NEVER HERE

TOP OF DETECTOR

ACCEPTABLE HERE

150-300mm

SMOKE ALARM ABOVE
TOP OF DOOR OPENING

20cm

STUB WALL

SOFFIT

111-281 English new  7/25/01  4:24 PM  Page 3

Summary of Contents for CC

Page 1: ... Procedures 7 Limited Warranty Table Of Contents CB CC CEC Ionisation type sensor Smoke Alarm Features Models CB CC and CEC are ionisation type smoke alarms Unique battery missing feature The smoke alarm will not attach to the mounting bracket if a battery is not in the battery pocket Low battery signal The smoke alarm will sound a short beep about once a minute if the battery needs to be replaced...

Page 2: ... a room should be further than 7 5m from the nearest smoke alarm This may require additional smoke alarms Where there are rooms other than bed rooms or toilets on either side of a bedroom a smoke alarm should be sited midway between the doors to these rooms For the highest level of protection install smoke or heat alarms in all other rooms except bath rooms or toilets FIGURE 1 Siting of Smoke Alar...

Page 3: ...t site an ionisation smoke alarm in an area where particles of combustion are normally present such as kitchens or garages An ionisation type smoke alarm with a FALSE ALARM CONTROL feature or a photoelectric type smoke alarm should be used to minimize nuisance alarms Do not site a smoke alarm in dusty or dirty areas SUCH AN INSTALLATION CANNOT BE RELIED UPON An accumulation of dust and dirt in the...

Page 4: ...es end to end into the battery pocket observing polarity 10 Position smoke alarm to mounting bracket and turn clockwise The smoke alarm will lock into place To engage tamper resist feature insert pin into notch on edge of smoke alarm and mounting plate NOTE Smoke alarm will not mount to bracket if battery is not installed 11 Test smoke alarm See Testing Your Smoke Alarm DO NOT connect this smoke a...

Page 5: ... from mounting plate 2 From back of smoke alarm lift tab to open battery pocket door Models CB and CC only Remove bat tery from pocket Disconnect and discard drained battery from battery connector 3 Connect a fresh 9 volt battery to connector The battery will fit only one way Be sure battery connec tor is securely attached to battery terminals NOTE For Model CEC replace safety light batteries with...

Page 6: ...m and on every level of the home Smoke may not reach the smoke alarm for many reasons For example if a fire starts in a remote part of the home on another level in a chimney wall roof or on the other side of a closed door smoke may not reach the smoke alarm in time to alert household members A smoke alarm will not promptly detect a fire EXCEPT in the area or room in which it is installed This smok...

Page 7: ...nship under normal residential use and service for a period of ten 10 years from date of purchase Maple Chase agrees to repair or replace at its option any defective smoke alarm or Ultralife U9VL J 9 volt bat tery when applicable provided that it is returned with postage prepaid and with proof of purchase date to Maple Chase This warranty does not cover damage resulting from accident misuse abuse ...

Reviews: