background image

Page 1 of  36

L

NOTICE

All information, documentation, and specifications contained in this manual are subject to change
without prior notice by the manufacturer.

FW-C2Z, FW-C4Z and FW-C4EZ 

Microprocessor Based - Fire Alarm Control Panels

INSTALLATION  and  OPERATION MANUAL

©1999 by NAPCO Security Systems, Inc.
Printed in CANADA, September 23, 1999

LT-636NAP Rev.1

   (Operating Instruction is 

NP-779NAP Rev.1

)

Summary of Contents for FW-C2Z

Page 1: ...re subject to change without prior notice by the manufacturer FW C2Z FW C4Z and FW C4EZ Microprocessor Based Fire Alarm Control Panels INSTALLATION and OPERATION MANUAL 1999 by NAPCO Security Systems...

Page 2: ...Y MODULE FW RB4 or FW RB8 TERMINAL CONNECTIONS Page 19 of 36 7 5 DACT DIALER MODULE FW DACT TERMINAL CONNECTIONS Page 20 of 36 7 6 POLARITY REVERSAL and CITY TIE MODULE MODEL FW RPM TERMINAL CONNECTIO...

Page 3: ...W RPM City Tie Module Page 14 of 36 Fig 10 General Field Wiring Considerations Page 15 of 36 Fig 11 Main Fire Alarm Module Terminal Connections Page 16 of 36 Fig 11a Main Fire Alarm Module Terminal Co...

Page 4: ...n Circuits are added T Each Initiating Circuit is configurable as a Normal or Verified Alarm In addition on a Class B FW C4Z or FW C4EZ Initiating Circuit 3 may be a Waterflow Zone as may Initiating C...

Page 5: ...bally all or none configured as Class A Style D as described in the Configuration Section This operation uses odd and even pairs of two wire Class B Style B circuits to make one four wire Class A Styl...

Page 6: ...2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 Page 6 of 36 3 0 SYSTEM COMPONENTS Model FW C2Z C4Z Fire Alarm Control Panel Model FW RPM City Tie Module Model FW C4EZ Fire Alarm Control Panel Model FW E...

Page 7: ...or two Class A Style D Initiating Circuits and 2 Power Limited Class A B Style Z Y Notification Circuits 1 70 amperes each 5 amperes total with individual trouble indicators Common Alarm Trouble Rela...

Page 8: ...OLE 12 4 3 8 7 8 15 8 1 8 1 14 1 8 3 3 3 1 4 1 6 x 5 16 SCREW KNOCKOUT 8 7 18 1 1 5 8 FINISH PAINTED MATERIAL 18GA 0 048 THICK COLD ROLLED STEEL Page 8 of 36 Fig 1 FW C2Z or FW C4Z Enclosure Installat...

Page 9: ...DOOR 4 5 1 BACKBOX SIDE VIEW FLUSH BACKBOX DOOR 16 5 WALL WALL 32 7 DIA HOLE 7 8 15 16 5 16 14 3 11 1 2 14 1 5 4 3 1 2 1 1 7 8 14 1 8 1 7 8 KNOCKOUT 12 2 1 8 3 1 2 8 3 4 2 6 x 5 16 SCREW MATERIAL BACK...

Page 10: ...W C4Z Module Mounting Locations 5 0 MODULE MOUNTING LOCATIONS The FW C2Z FW C4Z and FW C4EZ fire alarms come pre assembled with all components and boards except for Adder Modules Module installation l...

Page 11: ...F HEX SPACER 6 32 x 7 8 SCREW 6 32 x 1 4 DISPLAY PLATE BACKBOX ZONE ADDER MODULE FW EZM4 MAIN FIRE ALARM MODULE RELAY MODULE NOTE 1 NOTES 1 RELAY MODULE MAY BE FW RB4 OR FW 4B8 2 ONLY ONE OF FW DACT...

Page 12: ...P Switch Setting Zone Adder Module On an FW C4EZ only remove the jumper on JW4 if a FW EZM4 Zone Expansion is installed The Zone Adder Module is plugged into P6 P7 Relay Module Remove the jumper on JW...

Page 13: ...ing the 4 or 8 relays are controlled by Initiating Circuits 1 to 8 respectively This is configured by selecting JW1 Initiating Circuit 1 controls Relay 1 JW2 Initiating Circuit 2 controls Relay 2 JW8...

Page 14: ...information 6 5 POLARITY REVERSAL and CITY TIE MODULE MODEL FW RPM P1 Cable to P8 on the Main Fire Alarm Module JW1 Cut this jumper for Trouble transmission When this jumper is cut and a system troub...

Page 15: ...36 Fig 10 General Field Wiring Considerations 7 0 FIELD WIRING 7 1 GENERAL FIELD WIRING CONSIDERATIONS Because most of the Field Wiring is to the Main Board on the swinging DeadFront it is very import...

Page 16: ...NNECTIONS Wire devices to terminals as shown See wiring tables and Appendix A for compatible devices and Appendix C for specifications Caution Do not exceed power supply ratings FW C2Z FW C4Z total cu...

Page 17: ...EXAMPLES OF BOTH CLASS A AND B WIRING ARE SHOWN BUT ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION Page 17 of 36 Fig 11a Main Fire Alarm Module Terminal Connections continued...

Page 18: ...B WIRING ARE SHOWN BUT ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION Page 18 of 36 Fig 12 FW EZM4 Zone Expansion Module Terminal Connections 7 3 ZONE EXPANSION MODULE FW EZM4 TERMINAL CONNE...

Page 19: ...Page 19 of 36 7 4 RELAY MODULE FW RB4 or FW RB8 TERMINAL CONNECTIONS Note that only Relays 1 to 4 are present on the FW RB4 Fig 13 FW RB4 FW RB8 Relay Terminal Connections...

Page 20: ...NAL CONNECTIONS See Appendix for Module specifications Wire as shown using proper wire gauges Note that for use in the USA the installer MUST add an Atlantic Scientific Tel 407 725 8000 Model 24544 Pr...

Page 21: ...me delay fuse Power supply total current 2 75 A maximum Battery Fuse on Main Module F1 Replace with 10 Amp 1 1 4 Fast Acting Fuse Model FW C4EZ Electrical input ratings 120 VAC 60 Hz 2 5A Uses a 4 0A...

Page 22: ...ISTANCE 18AWG 16AWG 14AWG 12AWG Amperes ft m ft m ft m ft m Ohms 0 06 2350 716 3750 1143 6000 1829 8500 2591 30 0 12 1180 360 1850 567 3000 915 4250 1296 15 0 30 470 143 750 229 1200 366 1900 579 6 0...

Page 23: ...ntermittently and the Common Trouble LED should flash 3 Connect the batteries while observing correct polarity the red wire is positive and black wire is negative 4 All indicators should extinguish ex...

Page 24: ...Page 24 of 36 Fig 18 Indicators and Control Location 9 0 INDICATORS CONTROLS OPERATION Refer to the following LED Indicators and Control Switch locations...

Page 25: ...h a Remote Annunciator or if a Remote Annunciator reports a local trouble It is turned off if these conditions go away Fire Drill LED The Fire Drill Indicator turns on steady Amber while Fire Drill is...

Page 26: ...is transmitted Lamp Test Switch Activation of the Lamp Test momentary switch turns all front panel Indicators and the buzzer on Buzzer Silence Switch Activation of the Buzzer Silence momentary switch...

Page 27: ...nd the Common Alarm LED to illuminate Red Note Do not use Retard Operation with any external Retarding device maximum Retard may not exceed 120 seconds Non Latching Supervisory For Supervisory Devices...

Page 28: ...9 2 Auto Signal Silence Switch 9 3 4 off 3 off Disabled 4 off 3 on 5 Minutes 4 on 3 off 10 Minutes 4 on 3 on 20 Minutes Switch 9 4 Signal Silence Inhibit Switch 9 5 None 1 Minute Initiating Circuit S...

Page 29: ...After any Configuration Switches are changed it is necessary to perform a System Reset Only Indicating Circuit 4 may be configured for Visual Devices If Initiating Circuit 7 is configured as Waterflo...

Page 30: ...so on If Initiating Circuit 3 is first activated the Indication Circuits will sound for three bursts with additional activations sounding for one burst etc The initial burst interval denoting the coun...

Page 31: ...220 6269C 003 PSD 7130 70 201000 003 SIJ 24 NS4 220 6270C 003 PSD 7130 70 201000 005 SIJ 24 HSC 220R PSD 7128 70 201000 001 SLR 24 NS6 220 CERBERUS PYROTRONICS PSD 7126 70 201000 002 SLR 24 NS4 220 D1...

Page 32: ...D 3 HB 72 0 045mA 5451 B406B A A 0 12 mA SLR 24 NS6 220 HD 3 HB 3 0 045mA SLR 24 NS4 220 HD 3 HB 3 0 045mA SENTROL ESL SLR 24H NS6 220 HD 3 HB 3 0 045mA 429C S10A N A 0 10 mA SLR 24H NS4 220 HD 3 HB 3...

Page 33: ...AS 2415W 24 FR AS 241575W FR AS 2430W FR AS 2475W FR AS 24110W FR AS 2415C FW AS 2430C FW AS 2475C FW AS 24100C FW AH 24 R AH 24 WP R NS 2415W FR NS 241575W FR NS 2430W FR NS 2475W FR NS 24110W FR NS...

Page 34: ...ps max secondary M For Notification Circuits 24VDC unfiltered M For Notification Circuits 24VDC unfiltered 2 40 Amps max 5 Amps max M Battery 24VDC Gel Cell Sealed Lead Acid M Battery 24VDC Gel Cell S...

Page 35: ...pply for Annunciators etc ALARM Total currents Add above currents STANDBY A B Total Current Requirement ALARM B ______ Amps Battery Capacity Requirement STANDBY A ______ X 24 or 60 Hours ___ ALARM B _...

Page 36: ...IM THE PRODUCT THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED EVEN FAILED TO GIVE WARNING Therefore the installer should in turn IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN advise the consumer...

Reviews: