background image

spindown of engine/fan(s) as a result of ignition switch-off or shutdown by FPX103C as a result of an 
alarm (from either detectors or manual operate switch).  With the ignition off the unit enters low power 
mode and the ON LED will flash to conserve power. Single flash shows the spindown timer is still 
counting (fans still turning), then adopts a double flash “heartbeat” indicating that “parked mode” is 
active and extinguisher operation will be immediate on double alarm or manual operate.In “parked 
mode” (ignition off for longer than spindown delay) then the fuel solenoid will operate on first alarm and 
extinguisher immediately on second alarm.  
Switching on the ignition even for a short time will restart the spindown timer and it is also active on 
initial power-on. 

Spindown timer is selectable: NoAUTO, IMMEDIATE, 5 to 30 seconds, 5 sec granularity. 
A fault in one detector loop will cause the auto mode to fail (because of the double knock logic) 
however a manufacturing option can allow PARKED mode to auto operate the extinguisher after single 
loop alarm if the other loop is faulty. 

Manual operate command must also wait for the engine/fan spindown before extinguisher activation. 
After 125ms filter time the unit will confirm activation request by flashing 2ALARM=AUTO LED and 
internal beeper, fan and fuel solenoid shutdown relays are activated immediately. After spindown 
timeout the extinguisher will operate and beeper will go continuous. 

PANEL LED INDICATIONS: 

The panel layout has two distinct areas for extinguisher and detector status with separate LED flash 
pattern indications for each detection loop (1 and 2).  

Power On  (Green LED)

Detector Alarm (Red LED)  - inverse flash pattern indicating affected loop

Detector Loop Fault  (Red AMBER) - inverse flash pattern indicating affected loop

2 Alarms=Auto Active (Red LED)

Extinguisher Fault  (Red AMBER)

Internal sounder will operate on anything that requires user attention (alarm or fault). 

CONTROLS: 

Extinguisher manual operate button (behind tamper evidence tag) 
Auto mode time delay selector DIP switch on panel rear (delay = binary_value * 5 seconds).  
SW1-3  off-off-off = immediate, on-on-on = AutoDisabled, on-off-off=5sec, off-on-off=10sec, etc. 
SW4 on = vfc operates on single alarm, off = vfc operates on double alarm 

CONNECTIONS:   

BLOCK 1 (6 way) 
GND   
External Alarm Output (Power via 2A N.O. relay contact) 
GND   
Ignition input (sets auto PARKED mode when off) 
Power (11-32vdc via 4A fuse) 
GND 

BLOCK 2 (6 way) 

BLOCK 3 (6 way) 

Detector Loop1A 

FirexA 

Detector Loop1B 

FirexB 

Detector Loop2A 

GND   

Detector Loop2B 

VFC (2Amps Max)  

GND   

NO VFC (2Amps Max) COM 

Aux input 

VFC (2Amps Max) NC 