Kompact RU Installation Version 14/4/14
4
KOMPACT FIRE BOX IN A MASONRY
ENCLOSURE
2. FLOOR PROTECTOR REQUIREMENTS
AS/NZ2918 Section 3.3 states that if the heater is to be placed on or within
500mm of heat sensitive materials in the floor, then a
floor protector will be
required. This floor protector shall extend under the heater and not less than
300mm beyond the front of the fuel loading or ash removal openings. The width
of the floor protector shall be not less than the width of the appliance and shall
extend not less than 200mm from each side of the fuel loading or ash removal
openings unless it forms an abutment with a wall or heatshield at a lesser
distance.
The heater and floor protector must be fixed to the floor for seismic restraint.
Anchor points for the heater are provided through the 2 front feet of the unit.
2A FLOOR PROTECTOR REQUIREMENTS
SOLID CONCRETE FLOOR
HEAT SENSITIVE FLOOR
SOLID CONCRETE FLOOR
PROTECTOR/HEARTH
FIRE BREAST / WALL
A
FASCIA
B
Diagram 1