Series 1600
Heat Circulating Fireplace
Installation Instructions

Page 3 of 6

Alternative Configurations

The drawings on this page and the following page show alternative fireplace configurations that can be achieved 

with a Fire Magic heat circulating fireplace.  

Model 

No.

A

J

Min.

Min.

1634A

33

53

28

1636A

36

56

28

1642A

41

61

28

1648A

47

67

32

Drawings and dimensions depicting a fireplace that projects 

into the room with air inlets on the sides.

Drawing and dimensions depicting two 

fireplaces set side by side.

Model 

No.

A

Min.

Min.

1634A

33

120

28

1636A

36

126

28

1642A

41

136

28

1648A

47

148

32

Summary of Contents for 1600

Page 1: ...nforms with IBC IRC Insulation provided to prevent masonry cracking Page 1 of 6 Dimensions Model No Heating Capacity Cu Ft A B C D E F G H J Min K Min 1634A 5300 33 28 22 75 16 5 39 5 19 5 28 50 65 28 1636A 5800 36 28 25 75 16 5 42 5 19 5 31 50 68 28 1642A 6000 42 28 30 75 16 5 47 5 19 5 37 50 74 28 1648A 7000 48 29 36 75 20 5 53 5 23 5 42 54 80 32 Heating capacity ratings based on 20o F above zer...

Page 2: ...m masonry measurements Use these plans and charts to determine the masonry footprint of this particular installation The foundation should extend a minimum 6 beyond the masonry footprint on all sides It should be 12 or more in thickness depending on local conditions Check your local building codes The foundation should be poured concrete or solid masonry It is recommended that it be reinforced wit...

Page 3: ...e following page show alternative fireplace configurations that can be achieved with a Fire Magic heat circulating fireplace Model No A J Min K Min 1634A 33 53 28 1636A 36 56 28 1642A 41 61 28 1648A 47 67 32 Drawings and dimensions depicting a fireplace that projects into the room with air inlets on the sides Drawing and dimensions depicting two fireplaces set side by side Model No A J Min K Min 1...

Page 4: ...ed Drawing and dimensions depicting a corner fireplace The left side shows a straight front The right shows an angled front Model No A J Min K Min 1634A 33 65 56 1636A 36 68 56 1642A 41 73 56 1648A 47 79 72 Model No A L Min M Min N Min 1634A 33 44 44 62 1636A 36 46 47 65 1642A 41 49 51 69 1648A 47 55 60 78 Drawing and dimensions depicting two fireplaces set back to back A minimum of 4 inches of ma...

Page 5: ...s to be continued through the masonry to an air intake opening The minimum combustibles clearance for all parts of the ducts and their passageways is 1 inch The exterior air intakes may not be located at an elevation higher than the firebox The air intakes must pull the combustion air from the exterior of the dwelling or from spaces within the dwelling ventilated with outside air such as non mecha...

Page 6: ... masonry opening should be at least 1 less than the circulating fireplace opening to conceal the joint between the masonry and metal This joint should be packed with insulation Remember to allow for the openings for the air inlets and outlets Chimney and Flue Chimney and flue construction is the same as any other fireplace Either a masonry or a metal chimney may be used with a Fire Magic circulato...