background image

K & W Manufacturing Co., Inc.,

 23107 Temescal Canyon Road, Corona  CA  92883

951-277-3300 Phone     951-277-2070 FAX     www.k-and-w-mfg.com

Series 1600
Heat Circulating Fireplace
Installation Instructions

Page 5 of 6

Construction Details

Fire Magic Circulator:

Set the Fire Magic unit on the firebrick without mortar or other material underneath. Completely cover the unit with the 
insulation furnished. A thin mixture of mortar brushed on the unit will hold insulation in place. This insulation material is 
important. It provides an expansion layer between the metal of the circulator and the masonry, and helps prevent cracking.

WARNING: This insulation material contains fiberglass wool.  It may cause irritation to skin, eyes, and respiratory 
tract.  Avoid contact with eyes and skin. Protect yourself by wearing long sleeved, loose fitting clothing, gloves and 
eye protection when handling and applying material. (Do not tape sleeves or pants at wrists or ankles.)  As an extra 
precaution, you may choose to wear a disposable dust respirator at all times.  Wash with soap and warm water after 
handling.  Wash work clothes separately and afterwards wipe out washer.

Laying of Masonry: 

Lay masonry around and to the top of the unit. (See typical construction details on page 1). The masonry walls 
surrounding the circulator should be a minimum thickness of 4”. Leave channels for air passage as described in the 
following section on air inlets and outlets. The masonry face (front) may be built at this time or after the chimney is 
completed. Angle iron should be used in the masonry to support the single hot air outlet, and at the transition from the 
masonry to the flue liner for support of the chimney and flue.

A smoke shelf should be formed in the sloping space behind the unit. (See section view on page 1).  Be sure to use a 
layer of the insulation material between the unit and the fill used to form the shelf to prevent cracking.

Exterior Air Ducts:

Fire Magic circulators come with exterior (or combustion) air ducts built into the sides of the units.  Each duct has an 
8 square inch passageway which needs to be continued through the masonry to an air intake opening.  The minimum 
combustibles clearance for all parts of the ducts and their passageways is 1 inch.

The exterior air intakes may not be located at an elevation higher than the firebox. The air intakes must pull the 
combustion air from the exterior of the dwelling or from spaces within the dwelling ventilated with outside air such as non-
mechanically ventilated crawl or attic spaces. The exterior air intakes 

may not

 be located within the garage or basement 

of the dwelling.  The exterior air intakes should be covered with a corrosion-resistant screen of 1/4-inch mesh.

Air Inlets and Outlets: 

Channels must be left in the masonry for each inlet and outlet. 

All

 air inlets and outlets 

must be open

 to allow circulating 

airflow for the Fire Magic circulator to operate correctly. 

Failure to allow all inlets and outlets to circulate air could result in 

warping of the circulator, damage to the surrounding masonry, and voids the warranty.

 

The channels should be sized to fit the size of the Fire Magic circulator. If Fire Magic air grills 
or fan sets are used, simply match the size of the grill-mounting frame. When spaced masonry 
grilles (or some other inlet and outlet coverings) are desired, use the table at the right for opening 
requirements.  The two air inlets must provide at least the net square inches of open space 
specified for the model unit used. The single front outlet must provide at least the same net square 
inches of open space specified. 

 Insufficient open space allowances for air inlets and outlets will 

restrict air circulation, reduce the efficiency of the fireplace, and possibly damage the unit, voiding 
the warranty.

Each channel should be ”plastered” smooth to seal the walls of the channels to avoid any possible smoke and air 
leakage from voids in the masonry. The “plastering” also helps improve the airflow into and out of the unit. In addition, use 
additional insulation material in the joint between the masonry channel and the inlets and outlets to provide a better seal. 
This step helps to prevent air from moving directly from the inlet channels to the outlet channels. 

Model 

No.

Minimum 

combined 

sq. inch 
opening

1634A

70

1636A

70

1642A

80

1648A

110

Continued on page 6

Continued from page 2

Summary of Contents for 1600

Page 1: ...nforms with IBC IRC Insulation provided to prevent masonry cracking Page 1 of 6 Dimensions Model No Heating Capacity Cu Ft A B C D E F G H J Min K Min 1634A 5300 33 28 22 75 16 5 39 5 19 5 28 50 65 28 1636A 5800 36 28 25 75 16 5 42 5 19 5 31 50 68 28 1642A 6000 42 28 30 75 16 5 47 5 19 5 37 50 74 28 1648A 7000 48 29 36 75 20 5 53 5 23 5 42 54 80 32 Heating capacity ratings based on 20o F above zer...

Page 2: ...m masonry measurements Use these plans and charts to determine the masonry footprint of this particular installation The foundation should extend a minimum 6 beyond the masonry footprint on all sides It should be 12 or more in thickness depending on local conditions Check your local building codes The foundation should be poured concrete or solid masonry It is recommended that it be reinforced wit...

Page 3: ...e following page show alternative fireplace configurations that can be achieved with a Fire Magic heat circulating fireplace Model No A J Min K Min 1634A 33 53 28 1636A 36 56 28 1642A 41 61 28 1648A 47 67 32 Drawings and dimensions depicting a fireplace that projects into the room with air inlets on the sides Drawing and dimensions depicting two fireplaces set side by side Model No A J Min K Min 1...

Page 4: ...ed Drawing and dimensions depicting a corner fireplace The left side shows a straight front The right shows an angled front Model No A J Min K Min 1634A 33 65 56 1636A 36 68 56 1642A 41 73 56 1648A 47 79 72 Model No A L Min M Min N Min 1634A 33 44 44 62 1636A 36 46 47 65 1642A 41 49 51 69 1648A 47 55 60 78 Drawing and dimensions depicting two fireplaces set back to back A minimum of 4 inches of ma...

Page 5: ...s to be continued through the masonry to an air intake opening The minimum combustibles clearance for all parts of the ducts and their passageways is 1 inch The exterior air intakes may not be located at an elevation higher than the firebox The air intakes must pull the combustion air from the exterior of the dwelling or from spaces within the dwelling ventilated with outside air such as non mecha...

Page 6: ... masonry opening should be at least 1 less than the circulating fireplace opening to conceal the joint between the masonry and metal This joint should be packed with insulation Remember to allow for the openings for the air inlets and outlets Chimney and Flue Chimney and flue construction is the same as any other fireplace Either a masonry or a metal chimney may be used with a Fire Magic circulato...

Reviews: