background image

 

 

Page 1 of 10

 

T

OTAL

P

AC

2 Integrated Fire Protection System 

PAR-3 Control Panel 

 

 

FM-072G-0-05 C

 

Controls Section 

1.  Product Description

 

The Control Panel Section of the Self-Contained 

T

OTAL

P

AC

2

 

unit is an add-on cabinet that is installed on the top of the trim 
enclosure at the factory.  This cabinet is fabricated of Gauge 
14 steel, painted fire red with baked powder paint making it 
rustproof, the same finish as the Trim Enclosure. 

The Control Panel Section is provided with a locked stainless 
steel door on the front giving access to the basic controls of 
the Control Panel.  Once opened, the cabinet door gives 
access to the Contractor's Terminal Strip (refer to FIELD 
WIRING DIAGRAM for additional details), the control panel 
main board, emergency batteries and other related 
equipment.  Refer to Figures 1 and 2 for additional details. 

2. Self-contained 

T

OTAL

P

AC

2

 Unit (with Viking PAR-3 Model 

B-2 Control Panel) 

The Viking PAR-3 Model B-2 Control Panel is a supervised, 
24 Volt, microprocessor-controlled release control panel.  
The panel is designed to operate the electric release 
solenoid, in the release piping of deluge or preaction 
systems.   The panel is available for use with either 120VAC-
60Hz or 220VAC-50Hz power supplies.  The battery 
compartment can hold two 12 volt batteries which are 
charged by an internal battery charger.  Batteries are 
available to provide up to 90 hours of backup power during 
AC power failure. 

The PAR-3 panel can be used with a wide range of 
compatible initiating devices such as pull stations, heat 
detectors (including linear heat detectors), photo-electric and 
ionization smoke detectors. 
A dip switch 'Function Selector' allows field programming for 
one of four possible input/output combinations, of which only 
two are available and Listed for use with the 

T

OTAL

P

AC

2

 

System:  Single Hazard Two Zone and Single Hazard 
Crossed Zone.  
Changing the position of the dip switch will cause the panel to 
go on trouble condition. 

Warning !

  Only the two configurations above are 

Listed/Approved with the 

T

OTAL

P

AC

2

 Unit.  Changing the 

position of the factory set dip switches may eliminate the 
Fire Protection capabilities of the system and/or void 
Listing/Approval and Warranty.  Consult FireFlex Systems 
before making any change ! 

In fire conditions when an initiating device circuit (or 
predetermined combination of circuits) is energized, the panel 
activates the release and signaling circuits according to the 
'Function  Selector' setting. 
On the panel's display board, the appropriate Alarm, Trouble 
and Supervisory LED's will flash until the event has been 
acknowledged.  After depressing the Tone or Alarm Silence 
button, the LED will remain steadily illuminated until the panel 
is reset. 

3. Technical Data 

Approvals: 

The PAR-3

 

Control Panel when provided in the Control 

Panel Section of the 

T

OTAL

P

AC

2

 Unit forms an assembly 

that is Underwriters Laboratories Inc. Listed (Model B2 
for UL Listed systems & B-2C for ULC Listed systems) 
and Factory Mutual Research <FM> Approved.  Refer to 
GENERAL SECTION for additional details.

 

Cabinet: 

Vented enclosure: 

1 ½" to 3" Dia. Units:  36" x 20" x 14" 
4" & 6" Dia. Units: 46" x 24" x 14"  

Environment: 

Temperature:  32

o

F. (0

o

C) to 120

o

F (49

o

C) 

Humidity:  85% Relative Humidity (non-condensing) at 
86

o

F (30

o

C) maximum. 

Recommended nominal room temperature:  60-80

o

(15-27

o

C). 

AC Power:

 

PAR-3C: 120VAC, 50/60Hz, 1.2 amps. 

Wire size:  minimum #14 AWG with 600 Volt insulation. 
PAR-3E:  220/240VAC, 50/60Hz, 0.6 amps. 
Wire size: minimum #14 AWG with 600 Volt insulation. 

Battery: 

Lead Acid only 
Maximum charging circuit: 27.6 V, 1.5A 

Initiating Device (input) Circuits: 

Four style B (Class B)/Style D (Class A) circuits factory 
wired: Input 1:  Detection Circuit 
 

Input 2:  Detection Circuit 

 

Input 3:  Water flow (Alarm pressure switch) 

 

Input 4:  Supervisory circuit. 

Power limited circuitry 
Normal operating voltage:  24VDC (ripple = 1.0V p-p) 
Alarm current:  15mA minimum 
Short circuit current:  40mA maximum 
Maximum detector current in standby: 2mA (max) per 
zone 
Maximum loop resistance:  100 ohms 
End-of-Line resistor: 4,7K-½Watt (provided)  -  Note:  
leave EOL resistor provided on all unused circuits. 
Detector loop current is sufficient to ensure operation of 
one alarmed detector per zone. 
Supervisory current:  5mA (including EOL resistor) 
Heat Detectors:  Detection circuits allow for installation 
of any number of listed or approved normally open 
thermal detectors. 
Smoke Detectors:  Refer to Device Compatibility 
Document on our Web site for a list of compatible smoke 
detectors, information concerning the maximum number 
of smoke detectors allowed per zone, and standby 
requirements for the smoke detector used.   
Also, refer to appropriate Fire Protection Equipment 
Approval Guides. 

Summary of Contents for TOTALPAC 2 PAR-3

Page 1: ...fore making any change In fire conditions when an initiating device circuit or predetermined combination of circuits is energized the panel activates the release and signaling circuits according to the Function Selector setting On the panel s display board the appropriate Alarm Trouble and Supervisory LED s will flash until the event has been acknowledged After depressing the Tone or Alarm Silence...

Page 2: ... A second trouble will resound the buzzer Switch 3 Alarm Activate The Alarm Activate switch may be used to activate signaling circuits and relays Switch 4 System reset The Reset switch clears any activated output circuit If alarm or trouble conditions exist when the reset switch is pushed they will re activate the panel Front Panel Zone Status LEDs When the panel is activated zone status LEDs illu...

Page 3: ... PAR 3 Control Panel Refer to Device Compatibility Document on our Web site and appropriate Fire Protection Equipment Approval Guides 4 Wire all alarm initiating devices sequentially for proper supervision 5 Pull required conductors and drill knockouts as required Note The control panel motherboard is factory pre wired and programmed for the configuration selected at the time of purchase All field...

Page 4: ...ush door handle Figure 2 Typical Control Equipment Layout FM 072Q 0 19 C dwg NOTE Front door assembly not shown for clarity Spare Sprinkler Heads Storage Rack 12 heads capacity TBA Field Wiring Terminals Strip TBC TBR also when provided Typical Control Panel Motherboard Placement TBB Field Wiring Terminal Strip for 120 220 Vac Power Feed under protective cover Air Compressor Isolating Switch rated...

Page 5: ...ads Storage Rack 12 heads capacity TBA TBC TBR Field Wiring Terminals Strip PAR 3 Control Panel Motherboard Placement Emergency Batteries BATT EARTH MICRO FAIL DIP Switches for System Programming J9 Troubleshooting LEDs 3 Placement of optional Status Annunciator Module MEA or Fail Safe Timer Elevators J9 Battery connector AC Circuit Breaker OPT 1 OPT 2 Refer to labels description for detail FM 072...

Page 6: ...quire RESET to clear ALARM SILENCE Acknowledge for alarms and supervisories The ALARM SILENCE switch will silence the local piezo change any flashing alarm LEDs to steady and turn off the notification appliance circuits not the Releasing Circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARM ACTIVATE The ALARM ACTIVATE switch may be...

Page 7: ...he button identified ALARM SILENCE To select the previous zone press the button identified ALARM ACTIVATE a When selection of the disabled zones is completed release the button identified TONE SILENCE b The yellow lamp identified SYSTEM TROUBLE will flash Silence the audible signal by pressing the button identified TONE SILENCE 3 To reactivate the zones previously disabled repeat the procedure to ...

Page 8: ...that must be supplied by the secondary power source batteries to sustain the control panel operation for one hour Control Panel including a 4XZM Relay module with AC power lamp OFF System trouble lamp and audible signal ON 096 If using an extra 4XZM Relay module add 008 If using a 4XLM RZA 4X Driver Annunciator combination add 019 Number in use Device current see Device Compatibility Document for ...

Page 9: ...than 85 of rated voltage allow them to charge for 48 hours 3 If problem persists replace batteries Ground fault trouble Earth yellow LED ON 1 Remove field wiring from TBA Install dummy ELR 4 7K for 24V 2 2K for 12V 2 Remove both battery leads 3 If trouble clears connect one circuit at the time to pinpoint the problem 4 If trouble does not clear replace circuit board System Trouble LED ON Power tro...

Page 10: ...Page 10 of 10 TOTALPAC2 Integrated Fire Protection System PAR 3 Control Panel FM 072G 0 05 C ...

Reviews: