Page 1 of 10
T
OTAL
P
AC
2 Integrated Fire Protection System
PAR-3 Control Panel
FM-072G-0-05 C
Controls Section
1. Product Description
The Control Panel Section of the Self-Contained
T
OTAL
P
AC
2
unit is an add-on cabinet that is installed on the top of the trim
enclosure at the factory. This cabinet is fabricated of Gauge
14 steel, painted fire red with baked powder paint making it
rustproof, the same finish as the Trim Enclosure.
The Control Panel Section is provided with a locked stainless
steel door on the front giving access to the basic controls of
the Control Panel. Once opened, the cabinet door gives
access to the Contractor's Terminal Strip (refer to FIELD
WIRING DIAGRAM for additional details), the control panel
main board, emergency batteries and other related
equipment. Refer to Figures 1 and 2 for additional details.
2. Self-contained
T
OTAL
P
AC
2
Unit (with Viking PAR-3 Model
B-2 Control Panel)
The Viking PAR-3 Model B-2 Control Panel is a supervised,
24 Volt, microprocessor-controlled release control panel.
The panel is designed to operate the electric release
solenoid, in the release piping of deluge or preaction
systems. The panel is available for use with either 120VAC-
60Hz or 220VAC-50Hz power supplies. The battery
compartment can hold two 12 volt batteries which are
charged by an internal battery charger. Batteries are
available to provide up to 90 hours of backup power during
AC power failure.
The PAR-3 panel can be used with a wide range of
compatible initiating devices such as pull stations, heat
detectors (including linear heat detectors), photo-electric and
ionization smoke detectors.
A dip switch 'Function Selector' allows field programming for
one of four possible input/output combinations, of which only
two are available and Listed for use with the
T
OTAL
P
AC
2
System: Single Hazard Two Zone and Single Hazard
Crossed Zone.
Changing the position of the dip switch will cause the panel to
go on trouble condition.
Warning !
Only the two configurations above are
Listed/Approved with the
T
OTAL
P
AC
2
Unit. Changing the
position of the factory set dip switches may eliminate the
Fire Protection capabilities of the system and/or void
Listing/Approval and Warranty. Consult FireFlex Systems
before making any change !
In fire conditions when an initiating device circuit (or
predetermined combination of circuits) is energized, the panel
activates the release and signaling circuits according to the
'Function Selector' setting.
On the panel's display board, the appropriate Alarm, Trouble
and Supervisory LED's will flash until the event has been
acknowledged. After depressing the Tone or Alarm Silence
button, the LED will remain steadily illuminated until the panel
is reset.
3. Technical Data
Approvals:
The PAR-3
Control Panel when provided in the Control
Panel Section of the
T
OTAL
P
AC
2
Unit forms an assembly
that is Underwriters Laboratories Inc. Listed (Model B2
for UL Listed systems & B-2C for ULC Listed systems)
and Factory Mutual Research <FM> Approved. Refer to
GENERAL SECTION for additional details.
Cabinet:
Vented enclosure:
1 ½" to 3" Dia. Units: 36" x 20" x 14"
4" & 6" Dia. Units: 46" x 24" x 14"
Environment:
Temperature: 32
o
F. (0
o
C) to 120
o
F (49
o
C)
Humidity: 85% Relative Humidity (non-condensing) at
86
o
F (30
o
C) maximum.
Recommended nominal room temperature: 60-80
o
F
(15-27
o
C).
AC Power:
PAR-3C: 120VAC, 50/60Hz, 1.2 amps.
Wire size: minimum #14 AWG with 600 Volt insulation.
PAR-3E: 220/240VAC, 50/60Hz, 0.6 amps.
Wire size: minimum #14 AWG with 600 Volt insulation.
Battery:
Lead Acid only
Maximum charging circuit: 27.6 V, 1.5A
Initiating Device (input) Circuits:
Four style B (Class B)/Style D (Class A) circuits factory
wired: Input 1: Detection Circuit
Input 2: Detection Circuit
Input 3: Water flow (Alarm pressure switch)
Input 4: Supervisory circuit.
Power limited circuitry
Normal operating voltage: 24VDC (ripple = 1.0V p-p)
Alarm current: 15mA minimum
Short circuit current: 40mA maximum
Maximum detector current in standby: 2mA (max) per
zone
Maximum loop resistance: 100 ohms
End-of-Line resistor: 4,7K-½Watt (provided) - Note:
leave EOL resistor provided on all unused circuits.
Detector loop current is sufficient to ensure operation of
one alarmed detector per zone.
Supervisory current: 5mA (including EOL resistor)
Heat Detectors: Detection circuits allow for installation
of any number of listed or approved normally open
thermal detectors.
Smoke Detectors: Refer to Device Compatibility
Document on our Web site for a list of compatible smoke
detectors, information concerning the maximum number
of smoke detectors allowed per zone, and standby
requirements for the smoke detector used.
Also, refer to appropriate Fire Protection Equipment
Approval Guides.